FieldServer FS-8700-66 instruction manual Configuring the FieldServer as a GESNP Server

Models: FS-8700-66

1 29
Download 29 pages 60.45 Kb
Page 14
Image 14
5.Configuring the FieldServer as a GE_SNP Server

Page 14 of 29FS-8700-66_GE-SNP Manual

Page 14 of 29

5.Configuring the FieldServer as a GE_SNP Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a GE_SNP Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for GE_SNP communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual Node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Server Side Connection Descriptors

Section Title

 

 

Connections

 

 

Column Title

Function

Legal Values

Port

Specify which port the device is

P1-P8, R1-R23

 

connected to the FieldServer

 

Protocol

Specify protocol used

SNP

 

 

 

Baud*

Specify baud rate

110 – 115200, standard

baud rates only

 

 

Parity*

Specify parity

Even, Odd, None, Mark,

Space

 

 

Data_Bits*

Specify data bits

7, 8

 

 

 

Stop_Bits*

Specify stop bits

1

 

 

 

Handshaking*

Specify hardware handshaking

RTS, RTS/CTS, None

Poll Delay

Time between internal polls.

0-3200s, 1s

Example

//Server Side Connections

Connections

Port,

Protocol,

Baud,

Parity,

Handshaking

P1,

SNP,

19200,

Odd,

None

3Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com