McQuay Micro Tech Open Protocol Driver Manual

 

 

 

Page 25 of 35

 

 

 

 

 

 

 

 

 

 

 

 

 

Array

Read/

 

Number

Base

Device

 

 

 

Write/

Field Name

Scaling8

 

 

 

Location

of Bytes

Address

 

 

 

 

 

 

 

Both

 

 

 

 

 

Method

 

 

 

43

b

Clear Ckt#1 Alarm

1

0x091A

 

1

 

 

 

44

b

Evaporator Entering Water Temperature Setpoint

1

0x090D

 

2

 

 

 

45

b

Evaporator Leaving Water Temperature Setpoint

1

0x0905

 

2

 

 

 

46

b

Maximum Chilled Water Reset Setpoint

1

0x090C

 

2

 

 

 

47

b

Network Command

1

0x044F

 

1

 

 

 

48

b

Network Demand Limit

1

0x044D

 

1

 

 

 

49

b

Network Evaporator Leaving Water Temp Reset

1

0x044E

 

1

 

 

 

50

b

Reset Option Setpoint

1

0x090B

 

1

 

 

Table 6 - Equipment Type : Self-Contained Units (SCUs)

 

 

 

 

 

 

 

 

 

Array

Read/

 

 

Number

Base

 

Device

 

 

Write/

Field Name

 

 

Scaling9

 

 

Location

 

of Bytes

Address

 

 

 

 

 

 

 

Both

 

 

 

 

 

 

Method

 

 

1

r

Air Velocity

 

1

 

0x0434

1

 

 

 

2

r

Airflow Status

 

1

 

0x045C

1

 

 

 

3

r

Current Alarm

 

1

 

0x0801

1

 

 

 

4

r

Previous Alarm

 

1

 

0x1301

1

 

 

 

5

r

Building Static Pressure

 

1

 

0x0435

1

 

 

 

6

r

Compressor #1 Alarm

 

1

 

0x081C

1

 

 

 

7

r

Compressor #1 Operating Hours

 

2

 

0x08AF

1

 

 

 

9

r

Compressor #2 Alarm

 

1

 

0x081D

1

 

 

 

10

r

Compressor #2 Operating Hours

 

2

 

0x08B2

1

 

 

 

12

r

Compressor #3 Alarm

 

1

 

0x081E

1

 

 

 

13

r

Compressor #3 Operating Hours

 

2

 

0x08B5

1

 

 

 

15

r

Compressor #4 Alarm

 

1

 

0x081F

1

 

 

 

16

r

Compressor #4 Operating Hours

 

2

 

0x08B8

1

 

 

 

18

r

Compressor #5 Alarm

 

1

 

0x0820

1

 

 

 

19

r

Compressor #5 Operating Hours

 

2

 

0x08BB

1

 

 

 

21

r

Compressor #6 Alarm

 

1

 

0x0821

1

 

 

 

22

r

Compressor #6 Operating Hours

 

2

 

0x08BE

1

 

 

 

24

r

Control Temperature

 

1

 

0x0432

1

 

 

 

25

r

Cool Stage

 

1

 

0x043F

1

 

 

 

26

r

Cooling Control Status

 

1

 

0x044A

1

 

 

 

27

r

Dew Point Temperature

 

1

 

0x042F

1

 

 

 

28

r

Duct Static Pressure #1

 

1

 

0x0435

1

 

 

 

29

r

Duct Static Pressure #2

 

1

 

0x0434

1

 

 

 

30

r

Economizer Enable

 

1

 

0x045A

1

 

 

 

31

r

Economizer Operating Hours

 

2

 

0x08C4

1

 

 

 

33

r

Economizer Position

 

1

 

0x042E

1

 

 

 

34

r

Entering Water Temperature

 

1

 

0x042C

1

 

 

9See Appendix A.1.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Page 25
Image 25
FieldServer FS-8700-80 instruction manual Equipment Type Self-Contained Units SCUs