McQuay Micro Tech Open Protocol Driver Manual |
| Page 26 of 35 | |||||
|
|
|
|
|
|
|
|
| Array | Read/ |
| Number | Base | Device |
|
| Write/ | Field Name | Scaling9 |
| |||
| Location | of Bytes | Address |
| |||
|
|
| |||||
|
| Both |
|
|
| Method |
|
| 35 | r | Fan - High Speed Operating Hours | 2 | 0x08AC | 1 |
|
| 37 | r | Fan - Low Speed Operating Hours | 2 | 0x08A9 | 1 |
|
| 39 | r | Fan Operation | 1 | 0x0462 | 1 |
|
| 40 | r | Fan Speed | 1 | 0x0436 | 1 |
|
| 41 | r | Heat Stage | 1 | 0x043E | 1 |
|
| 42 | r | Heating Control Status | 1 | 0x044C | 1 |
|
| 43 | r | Heating Operating Hours | 2 | 0x08C1 | 1 |
|
| 45 | r | Leaving Water Temperature | 1 | 0x042D | 1 |
|
| 46 | r | Mixed Air Temperature | 1 | 0x042B | 1 |
|
| 47 | r | Motor Amps | 1 | 0x0436 | 1 |
|
| 48 | r | Motor Speed | 1 | 0x04BB | 1 |
|
| 49 | r | Network Communications Status | 1 | 0x0470 | 1 |
|
| 50 | r | Outdoor Air Damper Status | 1 | 0x045F | 1 |
|
| 51 | r | Outdoor Air Temperature | 1 | 0x0429 | 1 |
|
| 52 | r | Override Hours | 2 | 0x08C7 | 1 |
|
| 54 | r | Refrigerant Pressure | 1 | 0x0431 | 1 |
|
| 55 | r | Relative Humidity | 1 | 0x0431 | 1 |
|
| 56 | r | Return Air Temperature | 1 | 0x0428 | 1 |
|
| 57 | r | Space Temperature | 1 | 0x042A | 1 |
|
| 58 | r | Supply Air Temperature | 1 | 0x0427 | 1 |
|
| 59 | r | Supply Fan Status | 1 | 0x045E | 1 |
|
| 60 | r | Unit Enabled Status | 1 | 0x0488 | 1 |
|
| 61 | r | Unit Status | 1 | 0x043D | 1 |
|
| 62 | r | Variable Inlet Vane Position | 1 | 0x0436 | 1 |
|
| 63 | r | Water Flow Required | 1 | 0x0445 | 1 |
|
| 64 | r | Water Flow | 1 | 0x045B | 1 |
|
| 65 | r | Water Pump Start/Stop | 1 | 0x0461 | 1 |
|
| 66 | b | Building Static Pressure Setpoint | 1 | 0x0923 | 1 |
|
| 67 | b | Clear Alarm | 1 | 0x04CE | 1 |
|
| 68 | b | Clear Alarm Buffer | 1 | 0x048A | 1 |
|
| 69 | b | Control Mode | 1 | 0x044F | 1 |
|
| 70 | b | Control Temperature Source | 1 | 0x0926 | 1 |
|
| 71 | b | Cooling Control Deadband | 1 | 0x088D | 1 |
|
| 72 | b | Cooling Control Setpoint | 1 | 0x0907 | 1 |
|
| 73 | b | Cooling Supply Deadband | 1 | 0x0878 | 1 |
|
| 74 | b | Cooling Supply Setpoint | 1 | 0x090E | 1 |
|
| 75 | b | Dew Point Deadband | 1 | 0x094E | 1 |
|
| 76 | b | Dew Point Sensor Type | 1 | 0x0949 | 1 |
|
| 77 | b | Dew Point Setpoint | 1 | 0x094D | 1 |
|
| 78 | b | Duct Static Pressure Setpoint | 1 | 0x0917 | 1 |
|
| 79 | b | Duct Static/Building Static Pressure Deadband | 1 | 0x089B | 1 |
|
| 80 | b | Economizer (Air) Changeover Differential | 1 | 0x0932 | 1 |
|
| 81 | b | Economizer (Air) Changeover Temperature Setpoint | 1 | 0x0931 | 1 |
|