McQuay Micro Tech Open Protocol Driver Manual

 

Page 23 of 35

 

 

 

 

 

 

 

 

 

Array

Read/

 

Number

Base

Device

 

 

Write/

Field Name

Scaling7

 

 

Location

of Bytes

Address

 

 

 

 

 

 

Both

 

 

 

Method

 

 

39

r

Leaving Evaporator Water Temp. - Hi Resolution

1

0x0419

7

 

 

40

r

LED Front Panel

1

0x021F

1

 

 

41

r

Lift Pressure

1

0x0412

1

 

 

42

r

Liquid Injection Solenoid

1

0x0216

1

 

 

43

r

Liquid Line Refrigerant Temp. - Lo Resolution

1

0x0404

1

 

 

44

r

Liquid Line Refrigerant Temp. - Hi Resolution

1

0x041D

8

 

 

45

r

Liquid Subcool

1

0x0417

1

 

 

46

r

Load Solenoid

1

0x0211

1

 

 

47

r

Low Evaporator Pressure Limit

1

0x043B

1

 

 

48

r

Manual Amp Limit

1

0X043D

1

 

 

49

r

Manual Amp Limit Setpoint

1

0x0901

1

 

 

50

r

Maximum Amp Limit

1

0X043C

1

 

 

51

r

Motor Control Latch Relay

1

0x0213

1

 

 

52

r

Motor Control Relay

1

0x021E

1

 

 

54

r

Motor Current Amps

2

0x0435

1

 

 

55

r

Motor Current Percent

1

0x040C

1

 

 

56

r

Motor Temperature Switch

1

0x050E

1

 

 

58

r

Number of Starts

2

0X0432

1

 

 

59

r

Oil Delta Pressure

1

0X040D

1

 

 

60

r

Oil Feed Temp.

1

0x0409

1

 

 

61

r

Oil Gage Pressure

1

0x0415

1

 

 

62

r

Oil Heater

1

0x0215

1

 

 

63

r

Oil Pressure Differential Switch

1

0X050E

1

 

 

64

r

Oil Pump

1

0X021D

1

 

 

65

r

Oil Sump Temp.

1

0X040A

1

 

 

67

r

Operating Hours

2

0x0430

1

 

 

68

r

Panel Rocker Switch

1

0X050E

1

 

 

69

r

Remote Amp Limit

1

0X043E

1

 

 

70

r

Remote Chilled Water Reset

1

0x0439

1

 

 

71

r

Remote Reset or Amp Limit Signal

1

0X040B

1

 

 

72

r

Remote Start/Stop Switch

1

0X050F

1

 

 

73

r

Soft Load Limit

1

0X043A

1

 

 

74

r

Starter Fault Switch

1

0X050F

1

 

 

75

r

Starter Transition Switch

1

0X050F

1

 

 

76

r

Superheat

1

0x0416

1

 

 

77

r

Surge Guard Switch

1

0X050E

1

 

 

78

r

Unit Status

1

0x0424

1

 

 

79

r

Unload Solenoid

1

0x0210

1

 

 

80

r

Vanes Closed Switch

1

0X050F

1

 

 

81

r

Watchdog Output

1

0x0214

1

 

 

82

b

Clear Current Fault

1

0X042A

1

 

 

83

b

Comm Port Baud Rate

1

0x0801

1

 

 

84

b

Correct Checksum

1

0x0800

1

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Page 23
Image 23
FieldServer FS-8700-80 instruction manual McQuay Micro Tech Open Protocol Driver Manual