Appendix B. Error Messages

Those messages marked with an * are only printed once even if they occur repeatedly.

Error Message

Action

McQuay:#1 FYI. The MapDesc

The length of the Map Descriptor used to expose driver statistics is

too short. Set the length to at least 1000. You can ignore this

called <%s> is too short

message – the driver will abandon excess statistics.

 

McQuay:#2 FYI. You could

You can safely ignore this message. It is a prompt. Refer to

have used a MapDesc called

Appendix A.8.

<%s> to expose diagnostic info.

McQuay:#3 FYI. Normally

This is a reminder that a password is expected when a node is

defined. Refer to sections 4.3 or 5.2. Even though password

passwords are defined for each

node.

checking is not enforced when the driver is configured as a Server,

the driver expects one to be defined for every node.

 

McQuay:#4 Err. Node list if full.

A maximum of 100 McQuay device nodes can be configured per

Max=%d

FieldServer. If the limit is reached, call support.

 

A node has been provided with two passwords. This is either a

 

configuration error or two nodes with the same address are

McQuay:#5 Err. Node=%d has

connected to different ports. The driver can only store one password

more than one password.

per node address and cannot use the port number to differentiate

 

them. Re-program the McQuay devices to have the same passwords

 

if they have the same addresses.

*McQuay:#9 FYI. Device

Device Scaling is being applied and the driver doesn’t know how to

scale a variable. Please submit your configuration file with your

scaling method unknown.

request for support.

 

McQuay:#10 Err. Node=%s.

The driver doesn’t recognize the equipment type specified using the

PLC_Type parameter in the configuration file. Refer to Appendix A.3

Equip. type not recognized.

for a list of valid equipment types.10

McQuay:#11 Err. Node=%s.

Refer to Sections 4.3, 5.2. and Appendix A.310

Equip. Type not specified.

 

McQuay:#13 Err.

Refer to Appendix A.2 for a list of valid field names. Refer also to

MapDesc=%s. Field Name

Sections 4.4 or 5.3.

unknown.

 

McQuay:#14 Err.

Corrective action is required. When writing to a McQuay device using

MapDesc=%s. Max Len=1 for

direct addressing the length may only be 110

Writes with direct addr.

 

McQuay:#15 Err.

Neither a field name nor an address was specified. The driver does

MapDesc=%s. Field

not know what location to read. Specify a field name from Appendix

Name/Address Required.

A.2.10

McQuay:#16 Err.

Each Map Descriptor must be connected to a node. This is done by

MapDesc=%s. No Node.

specifying a node name. 10

McQuay:#17 Err.

The offset added to the length of the Map Descriptor extends beyond

MapDesc=%s. Md too short.

the Data Array. Increase the Data Array length. 10

McQuay:#18 Err.

When using ‘everything’ as a field name the Map Descriptor function

MapDesc=%s. Cannot write

must be Rdbc or Rdb as this is a read only function.10

'Everything'.

 

McQuay:#19 do diagnostic 3

Call FieldServer Technical Support. A developer diagnostic has been

McQuay:#20 do diagnostic 1

called and should not have been.

McQuay:#21 do diagnostic 2

 

10Correct the configuration by editing the CSV file and downloading it to the FieldServer, then reset the FieldServer for the changes to take effect.