McQuay Micro Tech Open Protocol Driver Manual

 

 

 

 

Page 24 of 35

 

 

 

 

 

 

 

 

 

 

 

 

 

Array

Read/

 

Number

Base

Device

 

 

 

Write/

Field Name

Scaling7

 

 

 

Location

of Bytes

Address

 

 

 

 

 

 

 

Both

 

 

 

 

 

Method

 

 

 

85

b

Leaving Evaporator Temperature Setpoint

 

1

0x0900

 

7

 

 

 

86

b

Maximum Chilled Water Reset Setpoint

 

1

0x0820

 

9

 

 

 

87

b

Network Amp Reset

 

1

0x0450

 

1

 

 

 

88

b

Network Chilled Water Reset

 

1

0X044F

 

1

 

 

 

89

b

Network Start Stop

 

1

0x0451

 

1

 

 

 

90

b

Reset Option

 

1

0x0822

 

1

 

 

 

91

b

Soft Reset

 

1

0x0204

 

1

 

 

 

92

b

Start Mode

 

1

0x0824

 

1

 

 

 

93

b

Startup Differential Temp.

 

1

0x0826

 

9

 

 

 

94

b

Shutdown Differential Temp.

 

1

0x0827

 

9

 

 

Table 5 - Equipment Type : 001ASC Reciprocating Chiller

 

 

 

 

 

 

 

 

Array

Read/

 

 

Number

Base

 

Device

 

 

Write/

Field Name

 

 

Scaling8

 

 

Location

 

of Bytes

Address

 

 

 

 

 

 

 

Both

 

 

 

 

 

 

Method

 

 

1

r

Active Chilled Water Temperature Setpoint

 

1

 

0x045A

4

 

 

 

2

r

Ckt#1 Condenser Pressure

 

2

 

0x0467

2

 

 

 

4

r

Ckt#1 Alarm Conditions: Capacity

 

1

 

0x1F13

1

 

 

 

5

r

Ckt#1 Alarm Conditions: Condenser Pressure

 

2

 

0x1F09

2

 

 

 

7

r

Ckt#1 Alarm Conditions: Evap Leaving Water Temp

2

 

0x1F0F

1

 

 

 

9

r

Ckt#1 Alarm Conditions: Evap Pressure

 

2

 

0x1F07

2

 

 

 

11

r

Ckt#1 Alarm Conditions: Fan Stage

 

1

 

0x1F14

1

 

 

 

12

r

Ckt#1 Alarm Conditions: Liquid Line Temperature

 

2

 

0x1F0D

10

 

 

 

14

r

Ckt#1 Alarm Conditions: Outside Air Temp

 

2

 

0x1F11

10

 

 

 

16

r

Ckt#1 Alarm Conditions: Suction Temperature

 

2

 

0x1F0B

10

 

 

 

18

r

Ckt#1 Current Alarm

 

1

 

0x08B9

1

 

 

 

19

r

Ckt#1 Current Alarm HourMinuteMonthDateYear

 

1

 

0x1F02

1

 

 

 

20

r

Ckt#1 Evaporator Pressure

 

2

 

0x0463

2

 

 

 

22

r

Ckt#1 Liquid Line Temperature

 

2

 

0x0479

10

 

 

 

24

r

Ckt#1 Status

 

1

 

0x0428

1

 

 

 

25

r

Ckt#1 Subcooling Temperature

 

2

 

0x04DF

2

 

 

 

27

r

Ckt#1 Suction Temperature

 

2

 

0x0475

10

 

 

 

29

r

Ckt#1 Superheat Temperature

 

2

 

0x04D7

2

 

 

 

31

r

Compressor #1 Operating Hours

 

2

 

0x0862

1

 

 

 

33

r

Compressor #1 Starts

 

2

 

0x086A

1

 

 

 

35

r

Evaporator Entering Water Temperature

 

2

 

0x046E

10

 

 

 

37

r

Evaporator Leaving Water Temperature

 

2

 

0x0461

10

 

 

 

39

r

Outdoor Air Temperature

 

2

 

0x047D

10

 

 

 

41

r

Stage of Cooling

 

1

 

0x042B

1

 

 

 

42

r

Unit Status

 

1

 

0x0427

1

 

 

8See Appendix A.1.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldServer.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldServer.com

Page 24
Image 24
FieldServer FS-8700-80 instruction manual Equipment Type 001ASC Reciprocating Chiller