McQuay Micro Tech Open Protocol Driver Manual Page 7 of 35
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldSer ver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldSer ver.com
4.2. Client Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port Specify which port the device is
connected to the FieldServer P1-P8, R1-R 2
1
Baud* Specify baud rate 300, 1200, 2400, 4800 and 9600
baud (Vendor limitation).
Parity* Specify parity Even (Vendor limitation)
Data_Bits* Specify data bits 7 (Vendor limitation)
Stop_Bits* Specify stop bits 1
Protocol Specify protocol used MCQ, McQuay
Handshaking* Specify hardware handshaking None
Poll Delay* Time between internal polls 0-32000 seconds, 1 second
Example
// Client Side Connections
Connections
Port ,Baud ,Parity ,Data_Bits ,Protocol ,Handshaking ,Poll_Delay
P1 ,9600 ,Even ,7 ,McQuay ,None ,0.100s
1
Not all ports shown are necessarily supported b y the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.