Friedrich 2003 service manual Outdoor thermostat does not cut off

Models: 2003

1 64
Download 64 pages 15.19 Kb
Page 41
Image 41
Outdoor thermostat does not cut off

PROBLEM

POSSIBLE CAUSE

TO CORRECT

 

 

 

 

 

 

 

Outdoor thermostat does not cut off

Defective thermostat - replace.

Unit does not heat

compressor at the preselected tem-

 

adequately.

perature and bring on heating element.

 

 

Fresh air or exhaust door open.

Check if operating properly. Instruct customer

 

 

on proper use of control.

 

Dirty filter.

Clean as recommended in Owner’s Manual.

 

Unit undersized.

Check heat rise across coil. Refer to perfor-

 

 

mance data sheet on heat rise at various

 

 

outdoor ambients. If heat rise is satisfactory,

 

 

check if insulation can be added to attic or

 

 

walls.

PROBLEM

 

POSSIBLE CAUSE

 

TO CORRECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incorrect wiring.

 

Refer to applicable wiring diagram.

 

 

 

Defective solenoid coil.

 

Check for continuity of coil.

 

Unit cools when

 

Reversing valve fails to shift.

 

Block condenser coil and switch unit to cooling.

 

 

 

 

Allow pressure to build up in system, then

 

heat is called for.

 

 

 

 

 

 

 

switch to heating. If valve fails to shift, replace

 

 

 

 

 

 

 

 

 

 

valve.

 

 

 

Inoperative system switch.

 

Check for continuity of system switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

PROBLEM

 

POSSIBLE CAUSE

TO CORRECT

 

 

 

 

 

 

 

Outdoor thermostat does not cut off

Defective thermostat — replace.

 

 

compressor at the preselected tempera-

 

 

 

 

Unit does not heat

ture and bring on the heating element.

 

 

 

 

 

 

 

 

 

 

adequately.

 

 

 

 

 

 

Fresh air or exhaust door open.

Check if operating properly. Instruct customer on

 

 

 

 

 

 

proper use of control.

 

 

Dirty filter.

Clean as recommended in Owner’s Manual

 

 

Unit undersized.

Check heat rise across coil. Refer to performance

 

 

 

 

data sheet on heat rise at various outdoor ambients. If

 

 

 

 

heat rise is satisfactory, check if insulation can be

 

 

 

 

added to attic or walls.

 

 

 

 

 

 

 

 

 

 

 

PROBLEM

 

POSSIBLE CAUSE

TO CORRECT

 

Unit cools when heat is called for.

Incorrect wiring. Defective solenoid coil. Reversing valve fails to shift.

Inoperative system switch.

Refer to applicable wiring diagram. Check for continuity of coil.

Block condenser coil and switch unit to cooling. Allow pressure to build up in the system, then switch to heating. If valve fails to shift, replace valve.

Check for continuity of system switch.

PROBLEM

POSSIBLE CAUSE

TO CORRECT

 

 

 

 

 

Heating capillary tube partially

Check for partially starved outer coil. Replace heating

 

restricted.

capillary tube.

Cooling is ad-

Check valve leaking internally.

Switch unit several times from heating to cooling.

 

Check temperature rise across the coil. Refer to

equate, but heating

 

 

specification sheet for correct temperature rise.

is insufficient.

 

Reversing valve failing to shift

Deenergize solenoid coil, raise head pressure, ener-

 

 

completely — bypassing hot gas.

gize solenoid to break loose. If valve fails to make

 

 

complete shift, replace valve.

41

Page 41
Image 41
Friedrich 2003 service manual Outdoor thermostat does not cut off