VERT-I-PAK®A - D SUFFIX CHASSIS SPECIFICATIONS

Model

V(E,H)A09

V(E,H)A12

V(E,H)A18

Voltage (V)

230 / 208

230 / 208

230 / 208

Refrigerant

R-22

R-22

R-22

Chassis Width

23.125"

23.125"

23.125"

Chassis Depth

23.125"

23.125"

23.125"

Chassis Height **

32.25"

32.25"

32.25"

Shipping W x D x H

26" x 28" x 35"

26" x 28" x 35"

26" x 28" x 35"

Supply Duct Collar ***

10"

10"

10"

Drain Connection

1/2" MPT

1/2" MPT

1/2" MPT

Drain Hose ****

12" long

12" long

12" long

Thermostat Harness

36" long

36" long

36" long

Power Cord

60" long

60" long

60" long

Min. Circuit Amps

 

See Chassis Nameplate

 

CFM Indoor

 

Page 15

 

Fan Speeds

2

2

2

Max. Duct ESP

.3 In. water

.3 In. water

.3 In. water

NOTES: ** Height includes 2" duct collar & isolators under unit. *** Factory collar accepts 10" fl ex duct.

MODELS

V(E,H)A09K25

V(E,H)A09K34

V(E,H)A09K50

V(E,H)A12K25

V(E,H)A12K34

V(E,H)A12K50

V(E,H)A18K25

V(E,H)A18K34

V(E,H)A18K50

 

 

 

 

 

 

 

 

 

 

Cooling Cap. (Btu/h)

9500/9300

9500/9300

9500/9300

11500/11300

11500/11300

11500/11300

17200/17000

17200/17000

17200/17000

Cooling Power (W)

950

950

950

1200

1200

1200

1911

1911

1911

SEER

10.0

10.0

10.0

10.0

10.0

10.0

10.0

10.0

10.0

Water Removal (Pts/h)

2.1

2.1

2.1

2.8

2.8

2.8

4.0

4.0

4.0

Cooling SHR

0.77

0.77

0.77

0.76

0.76

0.76

0.75

0.75

0.75

 

 

 

 

 

 

 

 

 

 

Heater Size (KW)

2.5

3.4

5.0

2.5

3.4

5.0

2.5

3.4

5.0

Heating Cap.(Btu/h)

8500/7000

11600/9500

17000/13900

8500/7000

11600/9500

17000/13900

8500/7000

11600/9500

17000/13900

Heating Power (W)

2500/2050

3500/2780

5000/4090

2500/2050

3500/2780

5000/4520

2500/2050

3500/2780

5000/4520

Heating Current (A)

11.9/11.2

15.9/14.6

22.6/20.6

11.9/11.2

15.9/14.6

22.6/20.6

11.9/11.2

15.9/14.6

22.6/20.6

 

 

 

 

 

 

 

 

 

 

Heating Cap.(Btu/h)

8000/7800

8000/7800

8000/7800

11200/11000

11200/11000

11200/11000

15700/15500

15700/15500

15700/15500

Heating Power (W)

950

950

950

1200

1200

1200

1830

1830

1830

Heating Current (A)

4.4/4.9

4.4/4.9

4.4/4.9

5.2/6.0

5.2/6.0

5.2/6.0

9.0/10.0

9.0/10.0

9.0/10.0

COP @ 470 F

3.0

3.0

3.0

3.0

3.0

3.0

2.4

2.4

2.4

 

 

 

 

 

 

 

 

 

 

Voltage (V)

230/208

230/208

230/208

230/208

230/208

230/208

230/208

230/208

230/208

LRA - Comp. (A)

20

20

20

26.3

26.0

26.3

45

45

45

Cooling Current (A)

4.4/4.9

4.4/4.9

4.4/4.9

5.5/6.1

5.2/6.0

5.2/6.0

7.6

7.6

7.6

MIN. Ckt. Amps (A)

15

20

30

15

20

30

15

20

30

Power Connection

 

POWER CORD

 

 

POWER CORD

 

POWER CORD WITH OPTION TO HARD WIRE

 

 

 

 

 

 

 

 

 

 

Refrigerant

R-22

R-22

R-22

R-22

R-22

R-22

R-22

R-22

R-22

Unit Width (in.)

23.125

23.125

23.125

23.125

23.125

23.125

23.125

23.125

23.125

Unit Depth (in.)

23.125

23.125

23.125

23.125

23.125

23.125

23.125

23.125

23.125

Unit Height* (in.)

32.25

32.25

32.25

32.25

32.25

32.25

32.25

32.25

32.25

Shipping Weight (lbs.)

125

125

125

135

135

135

155

155

155

 

 

 

 

 

 

 

 

 

 

Indoor CFM **

300

300

300

375

375

375

550

550

550

Fresh Air CFM**

60

60

60

60

60

60

60

60

60

Motor

230V, 1/4 HP

230V, 1/4 HP

230V, 1/4 HP

230V, 1/4 HP

230V, 1/4 HP

230V, 1/4 HP

230V, 1/4 HP

230V, 1/4 HP

230V, 1/4 HP

Motor Amps**

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

*Height includes 2" high duct collar and 5/8" isolators under unit. **Normal Value Dry Coil on High Speed @ .3" ESP.

Due to continuing research in new energy-saving technology, specifi cations are subject to change without notice.

Capacity rated at standard conditions:

COOLING–

950F DB/750F WB outdoor, 800F DB/670F WB indoor HEATING– (reverse cycle)

470F DB/430F WB outdoor, 700F DB/600F WB indoor

7

Page 7
Image 7
Friedrich V(E, H)A09K25 service manual VERT-I-PAKA D Suffix Chassis Specifications