FrontCaster

Feet

Opening for air conditioning from the bottom

(The opening should be in the shaded free-access area. It can’t be shared with the opening for cables out.)

Unit: mm (inch)

FIGURE 1-24SPARC Enterprise M9000 Server (Base Cabinet + Expansion Cabinet) + Power Cabinet Bottom View

1.2.2.4Ceiling Height

The minimum ceiling height for the SPARC Enterprise M8000/M9000 Server is 2.3m (7.5 feet), measured from the true floor or a raised floor, whichever is higher. The space above the server and its surroundings must not restrict the movement of cooling air between the air conditioner and the server.

Chapter 1 Physical and Network Specifications 1-29