1.2.3Planning Your Access Route
This section describes necessary considerations before you move the server to its installation destination.
1.2.3.1Space Required for System Transport
The access route must satisfy the requirements listed in TABLE
Each cabinet is packed with simple packaging or in a
If the cabinet weight exceeds the minimum withstand load for the transport equipment used, you can move the cabinet with its PSU and FAN (about 4 kg each) removed.
TABLE
|
|
|
|
|
| Minimum |
|
|
|
|
|
|
| withstand |
|
| Device |
|
| Minimum | Minimum | load of | Maximum |
| status | Minimum | Minimum | passage | elevator car | transport | inclination |
| during | door height | door width | width [mm | depth [mm | equipment | of access |
Name | transport 1 | [mm (inch)] | [mm (inch)] | (inch)] | (inch)] | [kg] 3 | route [˚ ] |
SPARC | Simple | 1900 (74.8) | 1000 (39.4) | 1200 (47.2) | 1500 (59.0) | 820 | 10 |
Enterprise | packaging1 |
|
|
|
|
|
|
M8000 Server | Without | 1900 (74.8) | 800 (31.5) | 1000 (39.4) | 1350 (53.1) | 690 | 10 |
| |||||||
| front and |
|
|
|
|
|
|
| rear doors |
|
|
|
|
|
|
| or side |
|
|
|
|
|
|
| panels |
|
|
|
|
|
|
| 2100 (82.7) | 1800 (70.9) | 1800 (70.9) | 1100 (43.3) | 830 | 10 | |
| Wooden2 | 2100 (82.7) | 1900 (74.8) | 1900 (74.8) | 1100 (43.3) | 980 | 10 |
| packing |
|
|
|
|
|
|
|
|
|
|
|
|
|
|