2.2.1Single-Phase Power Supplies
TABLE
| Power supply |
|
|
|
|
|
| Circuit | |
|
|
|
| Power | Apparent |
| Rush | Leak | breaker |
| Voltage |
| Frequency | consumption | power | Power | current | current | capacity |
Name | [V] | Phase | [Hz] | [kW] | [kVA] | factor | [mA] | [A] | |
|
|
|
|
|
|
|
|
|
|
SPARC | 200 to | Single | 50/60 | 10.5 2 | 11.0 2 | 0.9 or | 100 or | 4.1 or | 30 7 |
Enterprise | 240 |
| +2%, |
|
| higher | less 6 | less 6 |
|
M8000 Server | VAC |
|
|
|
|
|
|
|
|
| ±10% |
|
|
|
|
|
|
|
|
| 100 |
|
| 0.1 3 | - | - | - | - | - |
| VAC 3 |
|
|
|
|
|
|
|
|
| ±10% |
|
|
|
|
|
|
|
|
SPARC | 200 to |
|
| 21.3 4 | 22.4 4 | 0.9 or | 100 or | 4.1 or | 30 7 |
Enterprise | 240 |
|
|
|
| higher | less 6 | less 6 |
|
M9000 Server | VAC |
|
|
|
|
|
|
|
|
(base cabinet) | ±10% |
|
|
|
|
|
|
|
|
| 100 |
|
| 0.1 3 | - | - | - | - | - |
| VAC 3 |
|
|
|
|
|
|
|
|
| ±10% |
|
|
|
|
|
|
|
|
SPARC | 200 to |
|
| 42.6 5 | 44.8 5 | 0.9 or | 100 or | 4.1 or | 30 7 |
Enterprise | 240 |
|
|
|
| higher | less 6 | less 6 |
|
M9000 Server | VAC |
|
|
|
|
|
|
|
|
(base cabinet + | ±10% |
|
|
|
|
|
|
|
|
expansion | 100 |
|
| 0.1 3 | - | - | - | - | - |
cabinet) |
|
| |||||||
| VAC 3 |
|
|
|
|
|
|
|
|
| ±10% |
|
|
|
|
|
|
|
|
Power Cabinet | 200 to |
|
| 21.3 4 | 22.4 4 | 0.9 or | 100 or | 4.1 or | 30 7 |
SPARC | 240 |
|
|
|
| higher | less 6 | less 6 |
|
Enterprise | VAC |
|
|
|
|
|
|
|
|
M9000 Server | ±10% |
|
|
|
|
|
|
|
|
(base cabinet) 1 |
|
|
|
|
|
|
|
|
|
Chapter 2 Environmental and Electrical Specifications