Method of Securing the Device To the Floor Surface

(Example of securing the SPARC Enterprise M9000 Server in place)

Fixing bracket

Caster

Feet

850 (33.5)

171

(6.7)

1260 (49.6)

 

 

 

175

(6.9)

66 (2.6)

99 (3.9)

99 (3.9)

66 (2.6)

Unit: mm (inch)

Front

(Floor)

A-A cross-section

Fixing bracket: C230-4130-X514

Bushing: C230-4080-X003

Metal washer: F6-WB12-121

Metal washer: F6-WM12-121

Bolt: F6-B12-***121 (Bolt diameter: M12)

*** = Bolt length (mm)

The bolt length must be specified here.

Note: Consult with the company that constructed the building because the length depends on the structure of the building.

FIGURE 1-25Cabinet Stabilization Measure: Securing the Device to the Floor Surface

1-32SPARC Enterprise M8000/M9000 Servers Site Planning Guide • September 2007