2.2.2Three-Phase Delta Power Supplies

TABLE 2-5Specifications (Three-Phase Delta Power Requirements)

 

Power supply

 

 

 

 

 

 

Circuit

 

 

 

 

Power

Apparen

 

Rush

Leakage

breaker

 

Voltage

 

Frequency

consumption

t power

Power

current

current

capacity

Name

[V]

Phase

[Hz]

[kW]

[kVA]

factor

[A0-p]

[mA]

[A]

 

 

 

 

 

 

 

 

 

 

SPARC

AC200-

Three-

50/60

10.5 2

11.0 2

0.9 or

100 or

30 or

50 6

Enterprise

240 ±

phase

+2%, -4%

 

 

higher

less 5

less 5

 

M8000 Server

10%

delta

 

 

 

 

 

 

 

+ Power

AC100

Single

 

0.1 1

-

-

-

-

-

Cabinet

 

± 10% 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPARC

AC200-

Three-

 

21.3 3

22.4 3

0.9 or

170 or

40 or

80 6

Enterprise

240 ±

phase

 

 

 

higher

less 5

less 5

 

M9000 Server

10%

delta

 

 

 

 

 

 

 

(base cabinet)

AC100

Single

 

0.1 1

-

-

-

-

-

+ Power

 

± 10% 1

 

 

 

 

 

 

 

 

Cabinet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPARC

AC200-

Three-

 

42.6 4

44.8 4

0.9 or

170 or

40 or

80 6

Enterprise

240 ±

phase

 

 

 

higher

less 5

less 5

 

M9000 Server

10%

delta

 

 

 

 

 

 

 

(base cabinet +

AC100

Single

 

0.1 1

-

-

-

-

-

expansion

 

± 10% 1

 

 

 

 

 

 

 

 

cabinet) +

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Cabinet

1The 100V power supply is used only for the FST, and this specification applies only to use in Japan.

2This value is reached when four CMUs and four IOUs are installed.

3This value is reached when eight CMUs and eight IOUs are installed.

4This value is reached when 16 CMUs and 16 IOUs are installed.

5This value represents the current for each cable.

6This value represents the capacity of a unit main line switch for each power supply of the three-phase power supplies.

Chapter 2 Environmental and Electrical Specifications 2-7