GE AP13787 Horizontal Vent Terminal Location, Additional Considerations, Operating

Models: AP13787

1 36
Download 36 pages 55.45 Kb
Page 14
Image 14

Safety Instructions

Installing the water heater.

NOTICE: All pipe, fittings, solvent cement, primers and procedures must conform to American National Standards Institute and American Society for Testing and Materials (ANSI/ASTM) standards.

Horizontal Vent Terminal Location

The location of the vent terminal depends on the following minimum clearances and considerations (see illustration):

Instructions Installation Instructions

 

Soffit vents

 

 

4'

4'

 

Inside

 

 

 

corner

 

 

 

Electric

 

4'

Fresh

meter

18"

 

air

 

 

18"

 

4'

intake

 

3' above

 

 

 

if within 10'

 

4'

12" (Above grade/snow level)

window or vent

 

 

Twelve (12) inches above grade level and above normal snow levels.

Four (4) feet below, or four (4) feet horizontally from any door, window, soffit, under eave vent or gravity air inlet to the building or other appliances, or from gas or electric meters. Do not locate vent above walkways, doors, windows, air inlets, gas or electric meters or other equipment.

Three (3) feet above any forced air inlet located within ten

(10)feet. Any fresh or make-up air inlet such as for a dryer or furnace area is considered to be a forced air inlet.

Eighteen (18) inches from an inside corner formed by two exterior walls.

Operating

Caulk

Rising moisture will collect under eaves

Additional Considerations

Do Not install vent terminal under any patio or deck.

To help prevent moisture from freezing on walls and under eaves, do not locate vent terminal on the side of a building with prevailing winter winds.

Care and Cleaning

Inside corner

If soffit vent is too close, block off and install new vent at another location

Caulk

6' (1.83 m) caulk zone

(1.83 m) 6'

6' (1.83 m) caulk

zone or to edge of

window etc., startingCaulk within 6' (1.83 m)

Do Not terminate vent pipe directly on brick or masonry surfaces. Use a rust-resistant sheet metal backing plate (2 x 2 feet) behind vent. (See illustration.)

Do Not locate vent terminal too close to shrubbery, as flue gasses may damage them.

Caulk all cracks, seams and joints within six (6) feet of vent

Customer Service Troubleshooting Tips

RTV silicone caulk

4'

2 ft. sq. (60 x 60 m) sheet metal plate

brick or masonary surface is recomen

(1.22 m)

 

WARNING: Moisture in the flue gas will condense as it leaves the vent terminal. In cold weather this condensate can freeze on the exterior wall, under the eaves and on surrounding objects. Some discoloration to the exterior of the building is to be expected. However, improper location or installation can result in severe damage to the structure or exterior finish of the building.

terminal.

All painted surfaces should be primed to lessen the chance of physical damage. Painted surfaces will require maintenance.

Insulate vent pipe exposed to cold conditions (attics, crawl spaces, etc.) with inflammable material to help prevent moisture from accumulating in vent pipe.

Do Not extend exposed vent pipe outside of building.

14

Page 14
Image 14
GE AP13787 Horizontal Vent Terminal Location, Additional Considerations, Operating, Care and Cleaning