Installation Instructions
INSTALLATION—GAS CONNECTIONS
1PROVIDE ADEQUATE GAS SUPPLY
3INSTALL REGULATOR ONTO BURNER BOX BOTTOM
This cooktop is designed to operate on natural gas at 4″ of water column manifold pressure and 7″ of water column (W.C.) supply pressure. It is shipped from the factory set for natural gas. The convertible pressure regulator supplied with the unit must be connected in series with the manifold of the cooktop and must remain in series with the supply line regardless of whether natural or L.P. gas is being used.
FOR PROPER OPERATION, THE MAXIMUM INLET PRESSURE TO THE REGULATOR MUST BE NO MORE THAN 14″ OF WATER COLUMN PRESSURE. For checking the regulator, the inlet pressure must be at least 1″ W.C.. (or 3.4 KPA) greater than the
Screw the regulator onto the burner box bottom pipe connection. Make sure the top of the regulator is facing towards the cabinet front, easily accessible through the cabinet doors.
Pressure |
| |
Regulator |
| |
Coupling |
| |
Electrical | ||
Valve | ||
Outlet 12″ | ||
| ||
| Below | |
| Countertop |
regulator output setting. If the regulator is set for 4″ W.C. of water column pressure, the inlet pressure must be at least 5″ W.C. If the
4COMPLETE CONNECTION WITH A COUPLING
regulator is set for 10″ W.C., the inlet pressure must be at least 11″ W.C.. The gas supply line to the cooktop should be 1/2″ or 3/4″ pipe.
2 INSTALL REGULATOR
NEVER REUSE OLD CONNECTORS WHEN INSTALLING THIS COOKTOP.
WARNING: Never reuse old flexible connectors. The use of old flexible connectors can cause gas leaks and personal injury. Always use new flexible connectors when installing a gas appliance.
| Screw a section of pipe |
| Pressure |
|
|
|
|
|
|
|
|
|
|
| Regulator |
|
|
|
|
|
|
| |||
|
|
|
|
| ||||||||
| onto the inlet end of the |
|
|
|
|
|
|
|
|
|
|
|
| pressure regulator and |
|
|
|
|
|
|
|
|
|
|
|
| install the coupling. | Coupling |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
To reduce the likelihood of gas leaks, apply teflon tape or a thread compound approved for use with LP or Natural gases to all threaded connections.
Complete the connection between the regulator pipe coupling and the
Pressure |
| |
Regulator |
| |
Coupling |
| |
Electrical | ||
Valve | ||
Outlet 12″ | ||
| ||
| Below | |
| Countertop |
6