NX-8V2 Control 43
LOC PG DESCRIPTION DEFAULT PROGRAMMING DATA
111 28 Segment 3
1 = Fast Loop Response.
2 = Double End of Line Tamper zone.
3 = Trouble zone (Day zone).
4 = Cross Zone.
5 = Dialer Delay zone.
6 = Swinger zone.
7 = Restore reporting.
8 = Listen-In.
Segment 4
1 = Zone Activity Monitor.
2 = End of Line Resistor Defeat.
3 = Zone acts as Request to Exit input.
4 = Zone acts as access entry point (Do not enable this segment unless
configured with Access Control module)
5 -8 = Reserved.
Segment 5 RESERVED
LOCATIONS 112 – 169
EVEN NUMBERED Contains the event code sent for Contact ID or SIA and chosen from the list on pg 16. 4+2 Format Note: If 4+2
format is being used, the number programmed in this location will be sent as the upper hex digit. The digit should be
from 1 to 15 when using 4+2 formats. The zone ID or user ID will be the lower hex digit of the zone that is in alarm.
ODD NUMBERED The defaults listed below represent the five segments of each of those locations. Use the data from location 111 (table
above and pg 28)
LOC DESCRIPTION DEFAULT PROGRAMMING DATA
112 ZONE TYPE 2 ALARM EVENT CODE 2 __
113 ZONE TYPE 2 CHARACTERISTIC SELECT 2-125-78-0-0 __ __ __ __ __
114 ZONE TYPE 3 ALARM EVENT CODE 7 __
115 ZONE TYPE 3 CHARACTERISTIC SELECT 5-1245-5678-0-0 __ __ __ __ __
116 ZONE TYPE 4 ALARM EVENT CODE 5 __
117 ZONE TYPE 4 CHARACTERISTIC SELECT 45-125-5678-0-0 __ __ __ __ __
118 ZONE TYPE 5 ALARM EVENT CODE 5 __
119 ZONE TYPE 5 CHARACTERISTIC SELECT 457-125-5678-0-0 __ __ __ __ __
120 ZONE TYPE 6 ALARM EVENT CODE 4 __
121 ZONE TYPE 6 CHARACTERISTIC SELECT 0-1245-5678-0-0 __ __ __ __ __
122 ZONE TYPE 7 ALARM EVENT CODE 0 __
123 ZONE TYPE 7 CHARACTERISTIC SELECT 2-0-78-0-0 __ __ __ __ __
124 ZONE TYPE 8 ALARM EVENT CODE 1 __
125 ZONE TYPE 8 CHARACTERISTIC SELECT 1-13-378-0-0 __ __ __ __ __
126 ZONE TYPE 9 ALARM EVENT CODE 7 __
127 ZONE TYPE 9 CHARACTERISTIC SELECT 6-1245-5678-0-0 __ __ __ __ __
128 ZONE TYPE 10 ALARM EVENT CODE 2 __
129 ZONE TYPE 10 CHARACTERISTIC SELECT 24-5-78-0-0 __ __ __ __ __
130 ZONE TYPE 11 ALARM EVENT CODE 3 __
131 ZONE TYPE 11 CHARACTERISTIC SELECT 3-0-0-0-0 __ __ __ __ __
132 ZONE TYPE 12 ALARM EVENT CODE 5 __
133 ZONE TYPE 12 CHARACTERISTIC SELECT 457-125-45678-0-0 __ __ __ __ __
134 ZONE TYPE 13 ALARM EVENT CODE 4 __
135 ZONE TYPE 13 CHARACTERISTIC SELECT 0-12458-5678-0-0 __ __ __ __ _ _
136 ZONE TYPE 14 ALARM EVENT CODE 7 __
137 ZONE TYPE 14 CHARACTERISTIC SELECT 5-12456-5678-0-0 __ __ __ __ _ _
138 ZONE TYPE 15 ALARM EVENT CODE 5 __
139 ZONE TYPE 15 CHARACTERISTIC SELECT 457-1256-5678-0-0 __ __ __ __ __
140 ZONE TYPE 16 ALARM EVENT CODE 4 __
141 ZONE TYPE 16 CHARACTERISTIC SELECT 0-12456-5678-0-0 __ __ __ __ _ _
142 ZONE TYPE 17 ALARM EVENT CODE 7 __
143 ZONE TYPE 17 CHARACTERISTIC SELECT 5-1245-25678-0-0 __ __ __ __ __
144 ZONE TYPE 18 ALARM EVENT CODE 5 __
145 ZONE TYPE 18 CHARACTERISTIC SELECT 457-125-25678-0-0 __ __ __ __ __
146 ZONE TYPE 19 ALARM EVENT CODE 4 __
147 ZONE TYPE 19 CHARACTERISTIC SELECT 0-1245-25678-0-0 __ __ __ __ __
148 ZONE TYPE 20 ALARM EVENT CODE 7 __
149 ZONE TYPE 20 CHARACTERISTIC SELECT 6-1245-25678-0-0 __ __ __ __ __
150 ZONE TYPE 21 ALARM EVENT CODE 15 __
151 ZONE TYPE 21 CHARACTERISTIC SELECT 24-15-78 __ __ __ __ __
152 ZONE TYPE 22 ALARM EVENT CODE 20 __
153 ZONE TYPE 22 CHARACTERISTIC SELECT 24-15-78 __ __ __ __ __
154 ZONE TYPE 23 ALARM EVENT CODE 21 __
155 ZONE TYPE 23 CHARACTERISTIC SELECT 24-15-78 __ __ __ __ __