1.5.5 Remote PowerPause™ Relay Box (Optional)
The PowerPause ™ Relay Box can control up to two
1.5.6 Surge Protection Module (Optional)
Using
1.6 Standards Compliance
OVATION™ Series ATS systems have been tested and listed by Underwriters Laboratories (UL) to standard UL67. UL performs periodic factory inspections to ensure compliance with the engineering documentation. Call Factory if your installer needs the UL file number.
Each OVATION™ Series ATS complies with NFPA 70 (National Electric Code) Article 702 as an “automatic transfer switch for use in Optional Standby Systems.”
IMPORTANT: The OVATION™ Series ATS should NOT be used for emergency system (see NEC Articles 517 and 700), nor as a Legally Required System (see NEC Article 701), nor for primary power in place of the electric utility or in life support applications.
10