SECTION 2 – COMPATIBLE EQUIPMENT

2.1 Compatible Generators

In order for the OVATION™ Series ATS to function as designed, it must be connected to a permanently installed, automatic starting generator, with a continuous supply of fuel, such as gasoline, diesel, LPG or natural gas. Additionally, gasoline or diesel-powered generators must be equipped with automatic choke and electric/remote start. All OVATION™ Series ATS systems supports 2-wire (ON, +12V) or 4-wire (CRANK, ON, +12V, -12V) generator signaling.

Note: Many generators require additional control circuits to properly operate with OVATION™ Series ATS. Contact Gen/Tran or visit

http://www.gen-tran.com/content/support/installation_instructions.asp , see: Ovation™ Series ATS – Generator Connection Diagrams for additional information.

2.2 Compatible Circuit Breakers

Each OVATION™ Series ATS has been configured; factory tested and shipped with the UTILITY MAIN and GENERATOR MAIN circuit breakers installed. Compatible branch circuit breakers (supplied by installer) are as follows:

COMPATIBLE CIRCUIT BREAKER TYPES:

Siemens QAF (arc fault), QFH, QE, QEH, QFP, QNR, QNRH, QP, QPH, QF, QT, QPF (GFCI), QSAP (Surge Protector), HQP

Cutler-Hammer/Westinghouse Series BD, BR, BQ, GFC

Square D Series HOM*

GE Series THQL, THHQL (60 amp maximum)

*NOTE: Square D HOM series branch circuit breakers cannot be installed in the top right position on Models ATS2001D and ATS2001R. If you are planning to use Square D branch circuit breakers, please install them in other positions on the bus.

11

Page 11
Image 11
GenTran ATS2001R, ATS2002R, ATS2001D, ATS1001R manual Compatible Equipment, Compatible Generators, Compatible Circuit Breakers