Goodman Mfg dimensions GMVM96 Airflow Data - Heating Speeds, Product Specifications, SS-GMVM96

Models: GMVM96

1 12
Download 12 pages 12.64 Kb
Page 7
Image 7
GMVM96 Airflow Data — Heating Speeds

Product Specifications

GMVM96 Airflow Data — Heating Speeds

GMVM960603BX

(Rise Range: 20 - 50°F)

Adjust

 

CFM *

 

Rise (°F)

Tap

 

 

 

 

 

 

 

 

 

 

 

Minus(-)

 

855

 

62

Normal

 

950

 

56

 

 

 

 

 

Plus (+)

 

1,045

 

51

 

 

 

 

 

Minus(-)

 

945

 

56

 

 

 

 

 

Normal

 

1,050

 

51

 

 

 

 

 

Plus (+)

 

1,155

 

46

Minus(-)

 

1,053

 

50

 

 

 

 

 

Normal

 

1,170

 

45

 

 

 

 

 

Plus (+)

 

1,287

 

41

 

 

 

 

 

Minus(-)

 

1,143

 

46

 

 

 

 

 

Normal

 

1,270

 

42

 

 

 

 

 

Plus (+)

 

1,397

 

38

 

 

 

 

* @ .1" - .5" w.c. ESP

 

 

 

 

 

GMVM961005DX

 

(Rise Range: 35 - 65°F)

 

 

 

 

 

 

Adjust

 

CFM *

 

Rise (°F)

Tap

 

 

 

 

 

 

 

 

 

 

 

Minus(-)

 

1,629

 

54

 

 

 

 

 

Normal

 

1,810

 

49

 

 

 

 

 

Plus (+)

 

1,991

 

44

 

 

 

 

 

Minus(-)

 

1,665

 

53

 

 

 

 

 

Normal

 

1,850

 

48

 

 

 

 

 

Plus (+)

 

2,035

 

43

Minus(-)

 

1,701

 

52

Normal

 

1,890

 

47

 

 

 

 

 

Plus (+)

 

2,079

 

43

 

 

 

 

 

Minus(-)

 

1,746

 

51

 

 

 

 

 

Normal

 

1,940

 

46

 

 

 

 

 

Plus (+)

 

2,134

 

41

 

 

 

 

 

* @ .1" - .5" w.c. ESP

GMVM960805CX

Rise Range: 35 - 65°F)

Adjust

 

CFM *

 

Rise (°F)

Tap

 

 

 

 

 

 

 

 

 

 

 

Minus(-)

 

1,440

 

49

Normal

 

1,600

 

44

 

 

 

 

 

Plus (+)

 

1,760

 

40

 

 

 

 

 

Minus(-)

 

1,521

 

47

 

 

 

 

 

Normal

 

1,690

 

42

 

 

 

 

 

Plus (+)

 

1,859

 

38

Minus(-)

 

1,620

 

44

 

 

 

 

 

Normal

 

1,800

 

39

 

 

 

 

 

Plus (+)

 

1,980

 

36

 

 

 

 

 

Minus(-)

 

1,701

 

42

 

 

 

 

 

Normal

 

1,890

 

37

 

 

 

 

 

Plus (+)

 

2,079

 

34

 

 

 

 

* @ .1" - .5" w.c. ESP

 

 

 

 

 

GMVM961155DX

 

(Rise Range: 35 - 65°F)

 

 

 

 

 

 

Adjust

 

CFM *

 

Rise (°F)

Tap

 

 

 

 

 

 

 

 

 

 

 

Minus(-)

 

1,629

 

62

 

 

 

 

 

Normal

 

1,810

 

56

 

 

 

 

 

Plus (+)

 

1,991

 

51

 

 

 

 

 

Minus(-)

 

1,665

 

60

 

 

 

 

 

Normal

 

1,850

 

54

 

 

 

 

 

Plus (+)

 

2,035

 

49

Minus(-)

 

1,701

 

59

Normal

 

1,890

 

53

 

 

 

 

 

Plus (+)

 

2,079

 

48

 

 

 

 

 

Minus(-)

 

1,746

 

58

 

 

 

 

 

Normal

 

1,940

 

52

 

 

 

 

 

Plus (+)

 

2,134

 

47

 

 

 

 

 

* @ .1" - .5" w.c. ESP

Notes

All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.

For most jobs, about 400 CFM per ton when cooling is desirable.

Operation is recommended below .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only.

100% CFM shown. CFM will vary proportionally with the gas valve BTU/H input.

SS-GMVM96

www.goodmanmfg.com

7

Page 7
Image 7
Goodman Mfg dimensions GMVM96 Airflow Data - Heating Speeds, Product Specifications, SS-GMVM96