TYPICAL WIRING SCHEMATIC Ð 580D036-150

TYPICAL WIRING SCHEMATIC Ð 580D036-150

NOTES FOR 580D036-150 UNITS:

1. If any of the original wire furnished must be re- placed, it must be replaced with Type 90 C wire or its equivalent.

2. Three-phase motors are protected under pri- mary single phasing conditions.

3. Thermostat: HH07AT170, 172, 174 and

P272-2783

Subbase: HH93AZ176, 178 and P272- 1882, 1883

4. Set heat anticipator for ®rst stage at 0.14 amp, second stage at 0.2 amp.

5. Use copper conductors only.

6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from 230 v tap (RED) and connect to 200 v tap (BLU). Insulate end of 230 v tap.

7. When ECON assembly is installed move GRA wire from connection board (Y1) to GRA wire from PL6,5. Move ORN wire from connection board (Y2) to ORN wire from PL6,9 on ECON assembly.