PERFORMANCE DATA (cont)
ALTITUDE COMPENSATION* Ð 580D090-150
| 125,000, 180,000, | 250,000 BTUH | |||
| AND 224,000 BTUH | ||||
| NOMINAL INPUT | ||||
| NOMINAL INPUT | ||||
ELEVATION |
|
| |||
(ft) | Natural | Liquid | Natural | Liquid | |
Gas | Propane | Gas | Propane | ||
| |||||
| Ori®ce | Ori®ce | Ori®ce | Ori®ce | |
| Size² | Size² | Size² | Size² | |
31 | 41 | 30 | 38 | ||
2,000 | 32 | 42 | 30 | 39 | |
3,000 | 32 | 42 | 31 | 40 | |
4,000 | 32 | 42 | 32 | 41 | |
5,000 | 33 | 43 | 33 | 42 | |
6,000 | 34 | 43 | 34 | 43 | |
7,000 | 35 | 44 | 35 | 43 | |
8,000 | 36 | 44 | 36 | 44 | |
9,000 | 37 | 45 | 37 | 44 | |
10,000 | 38 | 46 | 38 | 45 | |
11,000 | 39 | 47 | 39 | 45 | |
12,000 | 40 | 47 | 40 | 46 | |
13,000 | 41 | 48 | 41 | 47 | |
14,000 | 42 | 48 | 42 | 47 |
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.
²Ori®ces available through your local distributor.
EVAPORATOR-FAN MOTOR EFFICIENCY
UNIT |
| MOTOR EFFICIENCY (%) |
580D036,048 | 75 | |
580D060 |
| 74 |
580D072 |
| 84 |
80 | ||
580D150 |
| 87 |
579F180 (3.7 | Hp) | 85.8 |
579F216 (5 Hp) | 87.5 | |
579F240 (7.5 | Hp) | 88.5 |
579F300 (10 Hp) | 89.5 |
NOTE: All
ALTITUDE COMPENSATION* Ð
ELEVATION | NATURAL GAS ORIFICE SIZE² | |
(ft) | Lo Heat | High Heat |
28 | 29 | |
2,000 | 29 | 29 |
3,000 | 29 | 30 |
4,000 | 29 | 30 |
5,000 | 30 | 30 |
6,000 | 30 | 30 |
7,000 | 31 | 31 |
8,000 | 31 | 31 |
9,000 | 31 | 31 |
10,000 | 32 | 32 |
|
|
|
*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.
²Ori®ces available through your local distributor.
ALTITUDE DERATING FACTOR* Ð
ALL UNITS
ELEVATION | MAXIMUM HEATING VALUE |
(ft) | (Btu/ft3) |
1,100 | |
1,050 | |
1,000 | |
950 | |
900 | |
|
|
*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above sea level. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.
Fan Performance Using Accessory Power Exhaust
54