ALTITUDE COMPENSATION* Ð 580D090-150

PERFORMANCE DATA (cont)

ALTITUDE COMPENSATION* Ð 580D090-150

 

125,000, 180,000,

250,000 BTUH

 

AND 224,000 BTUH

 

NOMINAL INPUT

 

NOMINAL INPUT

ELEVATION

 

 

(ft)

Natural

Liquid

Natural

Liquid

Gas

Propane

Gas

Propane

 

 

Ori®ce

Ori®ce

Ori®ce

Ori®ce

 

Size²

Size²

Size²

Size²

0-2,000

31

41

30

38

2,000

32

42

30

39

3,000

32

42

31

40

4,000

32

42

32

41

5,000

33

43

33

42

6,000

34

43

34

43

7,000

35

44

35

43

8,000

36

44

36

44

9,000

37

45

37

44

10,000

38

46

38

45

11,000

39

47

39

45

12,000

40

47

40

46

13,000

41

48

41

47

14,000

42

48

42

47

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.

²Ori®ces available through your local distributor.

EVAPORATOR-FAN MOTOR EFFICIENCY

UNIT

 

MOTOR EFFICIENCY (%)

580D036,048

75

580D060

 

74

580D072

 

84

580D090-120

80

580D150

 

87

579F180 (3.7

Hp)

85.8

579F216 (5 Hp)

87.5

579F240 (7.5

Hp)

88.5

579F300 (10 Hp)

89.5

NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi- ciency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.

ALTITUDE COMPENSATION* Ð

579F180-300

ELEVATION

NATURAL GAS ORIFICE SIZE²

(ft)

Lo Heat

High Heat

0-2,000

28

29

2,000

29

29

3,000

29

30

4,000

29

30

5,000

30

30

6,000

30

30

7,000

31

31

8,000

31

31

9,000

31

31

10,000

32

32

 

 

 

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes.

²Ori®ces available through your local distributor.

ALTITUDE DERATING FACTOR* Ð

ALL UNITS

ELEVATION

MAXIMUM HEATING VALUE

(ft)

(Btu/ft3)

0-2,000

1,100

2,001-3,000

1,050

3,001-4,000

1,000

4,001-5,000

950

5,001-6,000

900

 

 

*Derating of the unit is not required unless the heating value of the gas exceeds the values listed in the table above, or if the elevation exceeds 6000 ft. Derating conditions must be 4% per thousand ft above sea level. For example, at 4000 ft, if the heating value of the gas exceeds 1000 Btu/ft3, the unit will require a 16% derating. For elevations above 6000 ft, the same formula applies. For example, at 7000 ft, the unit will require a 28% derating of the maximum heating value per the National Fuel Gas Code.

Fan Performance Using Accessory Power Exhaust (579F180-300)

54

Page 54
Image 54