Bryant 580D manual ELECTRICAL DATA Ð 579F180-300

Models: 580D

1 72
Download 72 pages 58.37 Kb
Page 57
Image 57
ELECTRICAL DATA Ð 579F180-300

ELECTRICAL DATA Ð 579F180-300

 

NOMINAL

VOLTAGE

 

COMPRESSOR

 

 

OFM

 

IFM

POWER

COMBUSTION

 

POWER SUPPLY

 

RANGE

NO. 1

NO. 2

 

 

EXHAUST

FAN MOTOR

 

UNIT

VOLTAGE

 

 

 

 

 

 

 

 

 

(60 Hz)

Min

Max

RLA

 

LRA

RLA

 

LRA

Qty

Hp

FLA

FLA

FLA

LRA

FLA

 

MCA

 

MOCP²

 

 

 

 

(ea)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

180

208/230

187

254

61.0

 

266

Ð

 

Ð

3

1¤2

1.70

10.5/10.5

Ð

Ð

0.57

 

92/92

 

150/150

(3 phase)

 

 

4.6

18.8

0.57

 

96/96

 

150/150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

 

 

 

 

 

 

 

 

 

 

 

 

Ð

Ð

0.30

 

42

 

70

Tons)

414

508

28.0

 

120

Ð

 

Ð

3

1¤2

0.80

4.8

 

 

(3 phase)

 

 

2.3

6.0

0.30

 

45

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

216

208/230

187

254

35.6

 

198

28.2

 

160

3

1¤2

1.70

15.8/15.8

Ð

Ð

0.57

 

94/94

 

125/125

(3 phase)

 

 

4.6

18.8

0.57

 

98/98

 

125/125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

 

 

 

 

 

 

 

 

 

 

 

 

Ð

Ð

0.30

 

47

 

60

Tons)

414

508

17.8

 

99

14.1

 

80

3

1¤2

0.80

7.9

 

 

 

 

2.3

6.0

0.30

 

49

 

60

 

(3 phase)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

208/230

187

254

35.6

 

198

35.6

 

198

2

1

5.50

25.0/25.0

Ð

Ð

0.57

 

116/116

 

150/150

(3 phase)

 

 

4.6

18.8

0.57

 

121/121

 

150/150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

 

 

 

 

 

 

 

 

 

 

 

 

Ð

Ð

0.30

 

59

 

70

Tons)

414

508

17.8

 

99

17.8

 

99

2

1

2.80

13.0

 

 

 

(3 phase)

 

 

2.3

6.0

0.30

 

61

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

208/230

187

254

43.6

 

228

43.6

 

228

2

1

5.50

28.0/28.0

Ð

Ð

0.57

 

137/137

 

175/175

(3 phase)

 

 

4.6

18.8

0.57

 

142/142

 

175/175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

 

 

 

 

 

 

 

 

 

 

 

 

Ð

Ð

0.30

 

70

 

90

Tons)

414

508

22.1

 

114

22.1

 

114

2

1

2.80

14.6

 

 

 

(3 phase)

 

 

2.3

6.0

0.30

 

72

 

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA

Ð Full Load Amps

HACR

Ð Heating, Air Conditioning and Refrigeration

IFM

Ð Indoor (Evaporator) Fan Motor

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

NEC

Ð National Electrical Code

OFM

Ð Outdoor (Condenser) Fan Motor

RLA

Ð Rated Load Amps

*Used to determine minimum disconnect size per NEC. ²Fuse or HACR circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage = 452 + 464 + 455

=

3

1371

3

036-150 Only

180-300 Only

180-300 Only

= 457

Determine maximum deviation from average voltage. (AB) 457 - 452 = 5 v

(BC) 464 - 457 = 7 v

(AC) 457 - 455 = 2 v Maximum deviation is 7 v.

Determine percent voltage imbalance.

% Voltage Imbalance = 100 x

7

036-072 Only

090-150 Only

NOTES:

1.In compliance with NEC requirements for multimotor and combina- tion load equipment (refer to NEC Articles 430 and 440), the over- current protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

57

Page 57
Image 57
Bryant 580D manual ELECTRICAL DATA Ð 579F180-300