PERFORMANCE DATA (cont)

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) − 580D036-072

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

900

1200

1400

1600

1800

 

2000

2200

2400

2600

3000

 

 

Durablade Economizer

0.05

0.05

0.05

0.05

0.05

 

0.05

0.05

0.05

0.05

0.05

Parablade Economizer

0.08

0.10

0.17

0.26

0.33

 

0.34

0.36

0.40

0.44

Ð

LEGEND

FIOP − Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) − 580D090-150

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

2200

2500

3000

3500

4000

 

4500

5000

5500

6000

6250

 

 

Durablade Economizer

0.02

0.02

0.03

0.04

0.05

 

0.06

0.07

0.08

0.09

0.09

Parablade Economizer

0.21

0.25

0.35

0.49

0.61

 

Ð

Ð

Ð

Ð

Ð

LEGEND

FIOP − Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) − 579F180-300

COMPONENT

 

 

 

 

CFM

 

 

 

 

4500

5000

5400

6000

7200

7500

9000

10,000

11,250

 

Economizer

0.04

0.05

0.06

0.07

0.09

0.10

0.11

0.12

0.14

 

 

 

 

 

 

 

 

 

 

LEGEND

FIOP − Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts.

FAN RPM AT MOTOR PULLEY SETTINGS* Ð 580D036-150 AND 579F180-300

UNIT

 

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

 

0

1¤2

1

11¤2

2

 

21¤2

3

31¤2

 

4

41¤2

5

51¤2

6

 

 

 

580D036²

1000

976

952

928

904

 

880

856

832

 

808

784

760

Ð

Ð

580D048²

1185

1150

1115

1080

1045

 

1010

975

940

 

905

870

835

Ð

Ð

580D060²

1300

1260

1220

1180

1140

 

1100

1060

1020

 

980

940

900

Ð

Ð

580D072**

1460

1420

1380

1345

1305

 

1265

1225

1185

 

1150

1110

1070

Ð

Ð

580D090**

840

815

790

765

740

 

715

690

665

 

635

615

590

Ð

Ð

580D090²²

935

910

885

860

835

 

810

785

760

 

735

710

685

Ð

Ð

580D102**

935

910

885

860

835

 

810

785

760

 

735

710

685

Ð

Ð

580D120**

935

910

885

860

835

 

810

785

760

 

735

710

685

Ð

Ð

580D120²

1085

1060

1035

1010

985

 

960

935

910

 

885

860

835

Ð

Ð

580D150**

1080

1060

1035

1015

990

 

970

950

925

 

905

880

860

Ð

Ð

580D150²

1260

1220

1185

1155

1130

 

1100

1075

1045

 

1015

990

960

930

900

579F180**

 

 

1179

1150

1121

 

1093

1064

1035

 

1006

978

949

920

891

579F180²²

 

 

1559

1522

1488

 

1455

1422

1389

 

1356

1323

1289

1256

1227

579F216**

 

 

1038

1023

1001

 

979

956

934

 

912

890

868

846

817

579F216²²

 

 

1197

1185

1165

 

1145

1124

1104

 

1084

1064

1043

1023

994

579F240**

 

 

1225

1209

1187

 

1165

1143

1120

 

1098

1076

1053

1031

1022

579F240²²

 

 

1458

1434

1407

 

1381

1354

1328

 

1301

1275

1248

1222

1193

579F300**

 

 

1283

1269

1247

 

1225

1203

1182

 

1160

1138

1116

1095

1066

579F300²²

 

 

N/A

N/A

1551

 

1524

1497

1470

 

1443

1415

1388

1361

1332

*Approximate fan rpm shown.

²Indicates alternate motor and drive package. **Indicates standard motor and drive package. ²²Indicates alternate drive package only.

Due to belt and pulley size, pulley cannot be set to this number of turns open.

52

Page 52
Image 52
Bryant manual ACCESSORY/FIOP Static PRESSURE* in. wg − 580D090-150, ACCESSORY/FIOP Static PRESSURE* in. wg − 579F180-300