PERFORMANCE DATA (cont)

FAN PERFORMANCE Ð 579F180-300 UNITS

579F180 (15 TONS)

Air¯ow

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

0.2

 

 

 

0.4

 

 

 

 

0.6

 

 

 

 

 

 

0.8

 

 

 

 

1.0

 

 

1.2

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

 

Rpm

Bhp

 

Watts

 

Rpm

Bhp

 

Watts

 

Rpm

 

 

Bhp

 

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

801

1.05

933

 

890

1.26

1119

 

971

1.46

1297

1050

 

 

1.67

1483

1125

1.88

1670

1200

2.12

1883

4800

843

1.25

1110

 

928

1.47

1306

 

1006

1.68

1492

1081

 

 

1.90

1687

1153

2.13

1892

1223

2.36

2096

5100

885

1.47

1306

 

968

1.70

1510

 

1043

1.93

1714

1114

 

 

2.16

1918

1183

2.40

2131

1250

2.64

2345

5400

927

1.71

1519

 

1008

1.95

1732

 

1080

2.20

1954

1148

 

 

2.44

2167

1214

2.69

2389

1279

2.94

2611

5700

971

1.98

1758

 

1049

2.24

1989

 

1118

2.50

2220

1134

 

 

2.75

2442

1247

3.01

2673

1309

3.28

2913

6000

1016

2.28

2025

 

1091

2.55

2265

 

1158

2.83

2513

1222

 

 

3.10

2753

1282

3.36

2984

1342

3.64

3233

6300

1059

2.60

2309

 

1133

2.89

2567

 

1198

3.17

2815

1259

 

 

3.46

3073

1318

3.74

3321

1375

4.02

3570

6600

1104

2.96

2629

 

1174

3.26

2895

 

1239

3.56

3162

1297

 

 

3.86

3428

1355

4.15

3686

1405

4.40

3970

6900

1150

3.35

2975

 

1218

3.67

3259

 

1281

3.98

3535

1340

 

 

4.20

3730

1392

4.55

4040

1460

4.95

4350

7200

1194

3.77

3348

 

1260

4.10

3641

 

1325

4.40

3907

1390

 

 

4.65

4130

1440

5.10

4530

1510

5.30

4700

7500

1238

4.23

3758

 

1300

4.50

3996

 

1370

4.90

4351

1435

 

 

5.00

4440

1490

5.60

4970

Ð

Ð

Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

579F180 (15 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air¯ow

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4

 

 

 

1.6

 

 

 

 

1.8

 

 

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

 

Rpm

Bhp

 

Watts

 

Rpm

Bhp

 

Watts

 

Rpm

 

Bhp

 

Watts

 

 

 

 

 

 

 

4500

1275

2.39

2123

 

1349

2.70

 

2398

 

1421

3.03

 

2691

 

1490

 

3.39

 

3011

 

 

 

 

 

 

 

4800

1293

2.62

2327

 

1364

2.92

 

2593

 

1433

3.24

 

2877

 

1501

 

3.59

 

3188

 

 

 

 

 

 

 

5100

1316

2.90

2575

 

1382

3.18

 

2824

 

1448

3.49

 

3099

 

1514

 

3.86

 

3428

 

 

 

 

 

 

 

5400

1342

3.20

2842

 

1403

3.47

 

3082

 

1466

3.77

 

3348

 

1529

 

4.16

 

3694

 

 

 

 

 

 

 

5700

1370

3.54

3144

 

1429

3.81

 

3384

 

1487

4.11

 

3650

 

Ð

 

 

Ð

 

Ð

 

 

 

 

 

 

 

6000

1401

3.92

3481

 

1458

4.20

 

3730

 

1525

4.50

 

3776

 

Ð

 

 

Ð

 

Ð

 

 

 

 

 

 

 

6300

1430

4.30

3820

 

1490

4.55

 

4040

 

Ð

Ð

 

Ð

Ð

Ð

 

Ð

 

 

 

 

 

 

 

 

 

6600

1461

4.85

4305

 

1530

5.00

 

4440

 

Ð

Ð

 

Ð

Ð

Ð

 

Ð

 

 

 

 

 

 

 

 

 

6900

1500

5.35

4750

 

Ð

Ð

 

Ð

Ð

Ð

Ð

 

Ð

Ð

 

 

Ð

 

 

 

 

 

 

 

 

 

7200

Ð

Ð

Ð

Ð

Ð

Ð

 

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

 

 

 

 

 

 

 

 

 

7500

Ð

Ð

Ð

Ð

Ð

Ð

 

Ð

 

Ð

Ð

 

Ð

Ð

Ð

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp

Ð Brake Horsepower Input to Fan

FIOP

Ð

Factory Installed Option

Watts

Ð

Input Watts to Motor

*Standard low-medium static drive range is 891 to 1179 rpm. Alternate high static drive range is 1227 to 1550 rpm. Other rpms require a ®eld- supplied drive.

NOTES:

1.Static pressure losses (i.e., economizer) must be added to exter- nal static pressure before entering Fan Performance table. See Accessory/FIOP Static Pressure table on page 52 for more information.

2.Interpolation is permissible. Do not extrapolate.

3.Maximum continuous bhp is 4.25 and the maximum continuous watts are 3775. Extensive motor and drive testing on these units en- sures that the full horsepower range of the motor can be utilized with con®dence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure. Unit war- ranty will not be affected.