PERFORMANCE DATA (cont)

FAN PERFORMANCE Ð 579F180-300 UNITS (cont)

579F240 (20 TONS)*

Air¯ow

 

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

0.4

 

 

 

 

0.6

 

 

 

 

0.8

 

 

 

 

1.0

 

 

1.2

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

6000

767

1.80

1617

 

 

858

2.20

1932

 

 

944

2.50

2256

 

 

1026

2.90

2600

 

 

1104

3.30

2967

1181

3.80

3358

6500

817

2.20

1992

 

 

903

2.60

2329

 

 

985

3.00

2673

 

 

1062

3.40

3031

 

 

1136

3.80

3410

1209

4.30

3811

7000

869

2.70

2427

 

 

950

3.10

2787

 

 

1028

3.50

3151

 

 

1102

3.90

3527

 

 

1172

4.40

3919

1241

4.80

4331

7500

920

3.30

2919

 

 

998

3.70

3303

 

 

1073

4.10

3689

 

 

1143

4.60

4083

 

 

1210

5.00

4490

1275

5.50

4914

8000

973

3.90

3476

 

 

1047

4.30

3886

 

 

1119

4.80

4294

 

 

1186

5.30

4708

 

 

1250

5.70

5131

1313

6.20

5569

8500

1026

4.60

4102

 

 

1097

5.10

4635

 

 

1166

5.60

4967

 

 

1231

6.00

5401

 

 

1292

6.50

5843

1352

7.00

6297

9000

1079

5.40

4800

 

 

1147

5.90

5257

 

 

1214

6.40

5714

 

 

1276

6.90

6171

 

 

1336

7.40

6632

1393

7.90

7102

9500

1133

6.20

5576

 

 

1199

6.80

6058

 

 

1263

7.30

6540

 

 

1323

7.90

7018

 

 

1381

8.40

7500

1436

8.90

7988

10,000

1188

7.20

6432

 

 

1250

7.80

6939

 

 

1313

8.30

7444

 

 

1371

8.90

7946

 

 

1426

9.50

8449

Ð

Ð

Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

579F240 (20 TONS)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air¯ow

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

1.4

 

 

 

 

1.6

 

 

 

 

1.8

 

 

 

 

1.9

 

 

 

 

2.0

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

 

 

Rpm

Bhp

Watts

 

 

Rpm

Bhp

Watts

 

 

Rpm

Bhp

Watts

 

 

Rpm

Bhp

Watts

 

 

 

6000

1255

4.20

3772

 

 

1327

4.70

4206

 

 

1396

5.20

4658

 

 

1431

5.45

4884

 

 

1465

5.70

5110

 

 

 

6500

1279

4.70

4233

 

 

1348

5.20

4677

 

 

1415

5.80

5139

 

 

1449

6.10

5370

 

 

1482

6.40

5601

 

 

 

7000

1308

5.30

4762

 

 

1373

5.80

5215

 

 

1437

6.40

5686

 

 

1469

6.70

5922

 

 

1501

7.00

6157

 

 

 

7500

1339

6.00

5356

 

 

1401

6.50

5818

 

 

1462

7.00

6298

 

 

1493

7.25

6538

 

 

1523

7.50

6778

 

 

 

8000

1373

6.70

6024

 

 

1433

7.30

6495

 

 

1493

7.80

6966

 

 

1523

8.05

7202

 

 

Ð

Ð

Ð

 

 

 

8500

1410

7.60

6765

 

 

1467

8.10

7248

 

 

1524

8.70

7731

 

 

Ð

Ð

Ð

Ð

Ð

Ð

 

 

 

 

9000

1449

8.50

7584

 

 

1503

9.00

8033

 

 

Ð

Ð

Ð

Ð

Ð

Ð

Ð

 

 

Ð

Ð

 

 

 

 

9500

1488

9.40

8403

 

 

Ð

Ð

Ð

Ð

Ð

Ð

Ð

 

 

Ð

Ð

Ð

Ð

Ð

 

 

 

 

 

10,000

Ð

Ð

Ð

Ð

Ð

Ð

Ð

 

 

Ð

Ð

Ð

Ð

Ð

Ð

Ð

 

 

Ð

 

 

 

 

 

 

 

LEGEND

Bhp

Ð Brake Horsepower Input to Fan

FIOP

Ð

Factory-Installed Option

Watts

Ð

Input Watts to Motor

*Standard low-medium static motor drive range is 1002 to 1225 rpm. Al- ternate high static motor drive range is 1193 to 1458 rpm. Other rpms require a ®eld-supplied drive.

NOTES:

1.Static pressure losses (i.e., economizer) must be added to exter- nal static pressure before entering Fan Performance table. See Accessory/FIOP Static Pressure table on page 52 for more information.

2.Interpolation is permissible. Do not extrapolate.

3.Maximum continuous bhp is 8.7 for 208/230-v units and 9.5 for 460-v units. The maximum continuous watts are 7915 for the 208/230-v units and 8640 for the 460-v units. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with con®dence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

4.Deduct 0.2 in. wg static pressure for high heat units at or above 9000 cfm. Deduct 0.3 in. wg static pressure for high heat units at or above 10,000 cfm.

49

Page 49
Image 49
Bryant 580D 579F240 20 Tons Air¯ow External Static Pressure in. wg, Rpm Bhp Watts 6000, 9500, 10,000, 579F240 20 TONS