BASE UNIT DIMENSIONS Ð 579F240,300
NOTES:
1.Dimensions in ( ) are in millimeters.
2. Center of gravity.
3. Direction of air¯ow.
4.Ductwork to be attached to accessory roof curb or adapter only.
5.Minimum clearance:
a.Rear: 7 0 (2134) for coil removal. This dimension can be reduced to 4 0 (1219) if conditions permit coil removal from the top.
b.4 0 (1219) to combustible surfaces, all four sides (includes between units).
c.Left side: 4 0 (1219) for proper condenser coil air¯ow.
d.Front: 4 0 (1219) for control box access.
e.Right side: 4 0 (1219) for proper operation of damper and power exhaust (if so equipped).
f.Top: 6 0 (1829) to assure proper condenser fan operation.
g.Bottom: 14 (356) to combustible surfaces (when not using curb or adapter).
h.Control box side: 3 0 (914) to ungrounded surfaces
i.Control box side, 3 6 (1067) to block or concrete walls, or other grounded surfaces.
j.Local codes or jurisdiction may prevail.
6.With the exception of clearance for the condenser coil and the damper/power exhaust as stated in Note No. 5,
aremovable fence or barricade requires no clearance.
7.Dimensions are from outside of corner post. Allow 0
8.Do not locate adjacent units with the discharge facing economizer inlet.
UNIT |
|
|
| CORNER WEIGHT* |
|
|
| DIMENSION | ||||||||
| A | B |
|
| C |
| D |
| X | |||||||
579F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
lb | kg | lb | kg | lb | kg | lb | kg | mm | ||||||||
| ||||||||||||||||
240 | 520 |
| 235 | 508 |
| 230 | 532 |
| 241 | 640 |
| 290 |
| 965 | ||
300 | 527 |
| 239 | 545 |
| 247 | 578 |
| 262 | 600 |
| 272 |
| 1092 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Weights are for unit only (aluminum plate ®ns) and do not include op- tions or crating.
20