WARNING: An open bottom stationary engine generator set must be installed over noncombustible materials and shall be located such that it prevents combustible materials from accumulating under the generator set.

Several other factors should be carefully evaluated when selecting a location for installation:

1.For effective cooling and maintenance, the system should be mounted on a flat, smooth, noncombustible level surface. A concrete pad is ideal and provides a secure installation.

2.Installation should prevent water levels from reaching the generator. Drainage must be adequate to keep concrete pad free from standing water.

3.Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. If these items pose a problem, consider building a small fence or other break to protect the unit from accumulation of debris.

4.Installation should place the generator as close as possible to the fuel supply and transfer switch.

5.At least forty–eight (48) inches clearance must be provided on all sides for air flow.

6.Access must be provided to allow the enclosure covers to be opened or removed for service and maintenance.

7.Maximum Ambient temperature is 122°F (50°C).

 

Figure 3-2 Generator Mounting

 

 

Fuel Stub Up

 

 

 

GLC125 ONLY

 

 

 

Large Exhaust Area

 

 

B1

For GLC50, 60, 80, 100, 125 only

 

 

 

 

 

B

 

Fuel Stub Up

 

Electrical

 

(All except GLC125)

 

Stub Up

 

B2

 

 

30

A2

A2

A1

 

 

F1

E1

A

A

 

 

Table 3-3 Mounting Dimensions

Generator

A

A1

A2

B

B1

B2

E1

F1

GLC30

78.0

6.0

33.0

44.0

42.5

6.25

17.0

32.0

GLC35

78.0

6.0

33.0

44.0

42.5

6.25

17.0

32.0

GLC45

78.0

6.0

33.0

44.0

42.5

6.25

17.0

32.0

GLC50

118.0

6.0

38.0

44.0

42.5

6.25

17.0

32.0

GLC60

118.0

6.0

38.0

44.0

42.5

6.25

17.0

32.0

GLC80

118.0

6.0

38.0

44.0

42.5

6.25

17.0

32.0

GLC100

118.0

6.0

38.0

44.0

42.5

6.25

17.0

32.0

GLC125

118.0

6.0

38.0

44.0

42.5

6.25

17.0

32.0

3-2 Receiving & Installation

MN2408

Page 34
Image 34
Baldor GLC50, GLC35, GLC80, GLC125 manual Generator Mounting, Mounting Dimensions