Figure 4-6 Analog Fault Menu Loop Parameters

Fault Name

Input Analog

Fault

Setpoint Level

Setpoint Level

Action

Alarm Latch

Bypass On

Transient

 

Type

E=Enable

(Pick-up)

(Drop-out)

S=Shutdown

Y=Yes

Start

Delay (Sec)

 

 

 

D=Disable

 

 

A=Alarm

N=No

Y=Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N=No

 

Under Voltage

AC Voltage

E*

 

 

 

S

Y

Y*

5.0

Under Frequency

AC Frequency

E*

 

 

 

S

Y

Y*

5.0

Weak Battery

DC Voltage

E*

18.0

 

N/A

A*

Y

N*

3.0

Low Battery

DC Voltage

E*

25.6

 

N/A

A*

N

N*

120.0

Voltage

 

 

 

 

 

 

 

 

 

 

High Battery

DC Voltage

E*

30.4

 

N/A

A*

N

N*

10.0

Voltage

 

 

 

 

 

 

 

 

 

 

Low Engine Temp

Temp Sender

E*

95 °F

N/A

A*

Y

N*

5.0

High ENG Temp #1

Temp Sender

E*

198 °F

N/A

A

Y

Y

2.0

Alarm

 

 

 

 

 

 

 

 

 

 

High ENG Temp #2

Temp Sender

E*

206 °F

N/A

S

Y

Y

2.0

Shutdown

 

 

 

 

 

 

 

 

 

 

Low Oil Press #1

Press Sender

E*

30PSI

N/A

A

Y

Y*

2.0

Alarm

 

 

 

 

 

 

 

 

 

 

Low Oil Press #2

Press Sender

E*

20PSI

N/A

S

Y

Y*

2.0

Shutdown

 

 

 

 

 

 

 

 

 

 

* Indicates parameter is non-programmable.

 

 

 

 

 

 

 

 

 

 

Figure 4-7 Digital Fault Menu Loop Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault Name

Input #

Action

Alarm Latch

Polarity

Bypass On

Transient

 

 

 

 

 

S=Shutdown

Y=Yes

O=Open

Start

Delay (Sec)

 

 

 

 

 

A=Alarm

N=No

C=Close

Y=Yes

 

 

 

 

 

 

 

 

 

 

N=No

 

 

 

Low Oil Pressure

1

 

S

-

 

O

Y

0.5

 

 

High ENG TEMP

2

 

S

-

 

O

Y

1.0

 

 

Batt Chgr Input Fail

3

 

A

Y

C

N

30.0

 

 

Low Fuel Level

4

 

A

N

C

N

0.1

 

 

 

 

 

Figure 4-8 Calibration Menu Loop Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts A-B

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Volts A-B

 

Span XXX

XXXVAC

 

 

 

 

 

 

 

Volts B-C

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Volts B-C

 

Span XXX

XXXVAC

 

 

 

 

 

 

 

Volts C-A

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Volts C-A

 

Span XXX

XXXVAC

 

 

 

 

 

 

 

Volts A-N

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Volts A-N

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Volts B-N

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Volts B-N

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Volts C-N

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Volts C-N

 

Zero XXX

XXXVAC

 

 

 

 

 

 

 

Current A

 

Zero XXX

XXXAAC

 

 

 

 

 

 

 

Current A

 

Span XXX

XXXAAC

 

 

 

 

 

 

 

Current B

 

Zero XXX

XXXAAC

 

 

 

 

 

 

 

Current B

 

Span XXX

XXXAAC

 

 

 

 

 

 

 

Current C

 

Zero XXX

XXXAAC

 

 

 

 

 

 

 

Current C

 

Span XXX

XXXAAC

 

 

 

 

 

 

 

Battery Voltage

 

Span XXX

XX.X VDC

 

 

 

 

 

 

Engine Temperature

 

XXX

XXX C/F

 

 

 

 

 

 

 

Oil Pressure

 

XXX

XXXX PSI/KPA

 

 

 

 

 

 

4-20 Operation

MN2408

Page 66
Image 66
Baldor GLC50, GLC35 Fault Name Input Analog, 95 F, F Alarm, F Shutdown, Shutdown Indicates parameter is non-programmable