GLC Wire Size

 

 

 

 

 

 

 

 

 

 

Revision B

5–12–04

 

 

 

Circuit

Quantity per

Minimum

EDI Plant

Ampacity @125C

Breaker

Phase

Wire Gauge

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

15

1

#16

1

- #14 EPDM PER PHASE

40

20

1

#16

1

- #14 EPDM PER PHASE

40

30

1

#14

1

- #8 EPDM PER PHASE

90

40

1

#12

1

- #8 EPDM PER PHASE

90

50

1

#10

1

- #8 EPDM PER PHASE

90

60

1

#8

1

- #8 EPDM PER PHASE

90

70

1

#8

1

- #8 EPDM PER PHASE

90

80

1

#6

1

- #8 EPDM PER PHASE

90

90

1

#6

1

- #6 EPDM PER PHASE

125

100

1

#6

1

- #6 EPDM PER PHASE

125

110

1

#6

1

- #6 EPDM PER PHASE

125

125

1

#4

1

- #4 EPDM PER PHASE

170

150

1

#2

1

- #4 EPDM PER PHASE

170

175

1

#2

1

- #1 EPDM PER PHASE

265

200

1

#1

1

- #1 EPDM PER PHASE

265

225

1

1/0

1

- #1 EPDM PER PHASE

265

250

1

2/0

1

- #1/0 EPDM PER PHASE

305

300

1

4/0

1

- #2/0 EPDM PER PHASE

355

350

1

4/0

1

- #3/0 EPDM PER PHASE

410

400

2

#1

1

- #4/0 EPDM PER PHASE

475

450

2

1/0

2

- #1/0 EPDM PER PHASE

610

500

2

1/0

2

- #1/0 EPDM PER PHASE

610

600

2

3/0

2

- #2/0 EPDM PER PHASE

710

700

2

4/0

2

- #3/0 EPDM PER PHASE

820

800

3

2/0

2

- #4/0 EPDM PER PHASE

950

900

3

3/0

3

- #2/0 EPDM PER PHASE

1065

1000

3

3/0

3

- #3/0 EPDM PER PHASE

1230

1200

3

250

3

- #4/0 EPDM PER PHASE

1425

1400

4

4/0

4

- #4/0 EPDM PER PHASE

1900

1600

4

250

4

- #4/0 EPDM PER PHASE

1900

2000

5

250

5

- #4/0 EPDM PER PHASE

2375

2500

6

250

6

- #4/0 EPDM PER PHASE

2850

3000

7

250

6

- #250 EPDM PER PHASE

3180

4000

8

300

8

- #250 EPDM PER PHASE

4240

Wiring Diagrams Wiring diagrams for these generators are contained on the following pages of this appendix.