Baldor GLC125, GLC35, GLC80, GLC50 manual Air System Air System Checklist, Wind Barrier

Models: GLC50 GLC35 GLC125 GLC80

1 112
Download 112 pages 15.9 Kb
Page 27
Image 27

Air System

Air System Checklist

 

A. Air inlet faces the direction of prevailing winds.

 

B. Air outlet does not face noise sensitive areas without noise attenuating devices.

 

C. All heat loads have been taken into consideration in sizing air flow.

 

D. Gravity louvers face inward for air intake and outward for discharge.

 

E. Where electrically operated ventilation devices are used, power must be present under all

 

operating situations. Be certain these devices are on the emergency circuit.

 

The room in which the generator set is to be installed must have adequate air flow through it to

 

provide combustion air, and remove heat radiated from the engine, exhaust system and

 

generator. See Figure 2-14 for air flow calculations.

 

Figure 2-14 Air Flow Calculations

Radiator Cooling

The engine mounted radiator shown in Figure 2-8. With an engine mounted radiator cooling system, air movement is provided by the engine driven radiator fan. The consultant must design the inlet and outlet duct work and louvers to accommodate the air flow required. The radiator fan is limited in the amount of external static pressure it will tolerate. The maximum air restriction on the discharge side of the radiator is shown under the heading of Cooling System on the Engine Data Sheets. Cooling fan air flow is listed under Engine Data by dry type and water cooled exhaust manifold for 100 °F and 125 °F cooling systems.

The ideal setup for cooling air would be to arrange the inlet or inlets such that relatively clean, cool, dry air is drawn across the electrical switchgear, generator, and engine. The air is then drawn into the radiator fan, and is blown through the radiator and exhausted by duct work outside the building. Air inlets must be sized to minimize air restriction and provide the quantity of air required by the radiator fan, engine combustion air, and any other air exhausts which might be used in the room. On engine mounted radiator cooled systems, the engine mounted fan will handle 0.25” of water column. This is combined intake and exhaust restriction.

The room air intakes must be located so as to minimize drawing exhaust fumes and other outside contaminants into the room. Be very cautious about the location of the engine exhausts in relation to room air intakes. Also, when locating the inlet and outlet, the consultant should consider prevailing winds and noise. Motor operated louvers or properly designed and sized gravity louvers should be used on the air intake and exhaust to minimize static pressure drop.

Electric motorized louvers used with engine mounted radiators should be connected to the standby genset and controlled to open whenever the genset is running. Operable outlet louvers should be temperature actuated on remote radiator or heat exchanger cooled units. Louvers have resistance to air flow. Openings with louvers should be twice the area of an unobstructed opening to provide proper air flow. At times duct work is necessary to provide cooling air for the room, see Figure 2-15. Duct work must be sized and installed according to SMACNA Standards.

Wind Barrier

Wind blowing against air exhaust or intake openings of the genset room must be considered, especially where the radiator and fan are located on the engine. Wind blowing against an exhaust opening creates restriction to the fan. Wind blowing against intake openings can blow open gravity louvers causing low temperature and moisture problems in bad weather.

MN2408

General Information 2-17

Page 27
Image 27
Baldor GLC125, GLC35, GLC80, GLC50 manual Air System Air System Checklist, Wind Barrier