PERFORMANCE DATA (cont)

FAN PERFORMANCE Ð 580D036-150 VERTICAL DISCHARGE UNITS (cont)

580D072 (6 TONS)*

Air¯ow

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

0.1

 

 

 

 

0.2

 

 

 

 

0.4

 

 

 

0.6

 

 

0.8

 

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

Rpm

Bhp

Watts

1800

942

0.70

646

 

 

978

0.66

700

 

1063

 

0.82

 

771

1147

0.97

891

1248

1.20

1081

 

1322

1.33

1190

1900

982

0.80

739

 

 

1023

0.78

779

 

1097

 

0.91

 

843

1175

1.11

1006

1266

1.29

1156

 

1356

1.47

1310

2000

1022

0.91

835

 

 

1068

0.90

867

 

1132

 

1.01

 

924

1218

1.23

1106

1303

1.41

1258

 

1397

1.52

1353

2100

1063

0.99

916

 

 

1115

1.00

998

 

1180

 

1.17

 

1056

1261

1.35

1207

1340

1.53

1361

 

1428

1.66

1473

2200

1104

1.13

1039

 

 

1159

1.15

1081

 

1214

 

1.28

 

1148

1310

1.52

1353

1375

1.63

1447

 

1459

1.80

1595

2300

1130

1.26

1156

 

 

1202

1.29

1140

 

1248

 

1.38

 

1233

1358

1.69

1499

1410

1.72

1526

 

1488

1.93

1709

2400

1174

1.37

1258

 

 

1237

1.41

1224

 

1292

 

1.55

 

1378

1392

1.81

1604

1460

1.90

1683

 

1532

2.14

1892

2500

1201

1.48

1361

 

 

1272

1.53

1335

 

1335

 

1.71

 

1517

1427

1.94

1718

1518

2.16

1910

 

1575

2.35

2076

2600

1246

1.62

1491

 

 

1320

1.68

1482

 

1368

 

1.81

 

1604

1458

2.06

1823

1562

2.42

2136

 

1620

2.59

2283

2700

1285

1.75

1613

 

 

1361

1.82

1595

 

1400

 

1.91

 

1691

1490

2.19

1936

1602

2.64

2326

 

1666

2.85

2504

2800

1304

1.87

1726

 

 

1402

1.95

1639

 

1439

 

2.08

 

1840

1543

2.43

2145

1642

2.86

2512

 

Ð

Ð

Ð

2900

1345

2.07

1910

 

 

1446

2.16

1814

 

1477

 

2.16

 

1989

1585

2.65

2335

Ð

Ð

Ð

Ð

Ð

Ð

 

3000

1378

2.26

2084

 

 

1489

2.36

2032

 

1529

 

2.52

 

2223

1598

2.73

2444

Ð

Ð

Ð

Ð

Ð

Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580D072 (6 TONS)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air¯ow

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

 

 

 

 

1.4

 

 

 

 

1.6

 

 

 

 

 

 

 

 

 

 

 

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

 

 

Rpm

Bhp

Watts

 

Rpm

 

Bhp

 

Watts

 

 

 

 

 

 

 

 

 

 

1800

1395

1.46

1301

 

 

1475

1.56

1387

 

1542

 

1.71

 

1517

 

 

 

 

 

 

 

 

 

 

1900

1430

1.58

1404

 

 

1504

1.69

1499

 

1556

 

1.82

 

1613

 

 

 

 

 

 

 

 

 

 

2000

1459

1.67

1482

 

 

1532

1.82

1613

 

1588

 

1.97

 

1744

 

 

 

 

 

 

 

 

 

 

2100

1489

1.80

1595

 

 

1567

1.99

1761

 

1626

 

2.16

 

1910

 

 

 

 

 

 

 

 

 

 

2200

1528

1.95

1726

 

 

1603

2.17

1919

 

1666

 

2.37

 

2093

 

 

 

 

 

 

 

 

 

 

2300

1561

2.13

1884

 

 

1637

2.35

2076

 

1710

 

2.54

 

2272

 

 

 

 

 

 

 

 

 

 

2400

1584

2.28

2015

 

 

1671

2.55

2249

 

1756

 

2.70

 

2467

 

 

 

 

 

 

 

 

 

 

2500

1633

2.53

2232

 

 

1698

2.72

2405

 

Ð

 

Ð

 

Ð

 

 

 

 

 

 

 

 

 

 

2600

1675

2.77

2436

 

 

Ð

Ð

Ð

Ð

Ð

 

Ð

 

 

 

 

 

 

 

 

 

 

 

 

2700

Ð

Ð

Ð

Ð

Ð

Ð

Ð

 

Ð

 

Ð

 

 

 

 

 

 

 

 

 

 

 

 

2800

Ð

Ð

Ð

Ð

Ð

Ð

Ð

 

Ð

 

Ð

 

 

 

 

 

 

 

 

 

 

 

 

2900

Ð

Ð

Ð

Ð

Ð

Ð

Ð

 

Ð

 

Ð

 

 

 

 

 

 

 

 

 

 

 

 

3000

Ð

Ð

Ð

Ð

Ð

Ð

Ð

 

Ð

 

Ð

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp

Ð Brake Horsepower Input to Fan

FIOP

Ð

Factory-Installed Option

Watts

Ð

Input Watts to Motor

*Motor drive range is 1070 to 1460 rpm. All other rpms require a ®eld- supplied drive.

NOTES:

1.Boldface indicates ®eld-supplied motor and drive are required.

2.Values include losses for ®lters, unit casing, and wet coils. See page 52 for accessory/FIOP static pressure information.

3.Maximum continuous bhp is 2.40 and the maximum continuous watts are 2120. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®- dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit war- ranty will not be affected. See Evaporator-Fan Motor Performance table on page 55 for additional information.

4.Use of a ®eld-supplied motor may affect wire sizing. Contact your local representative for details.

5.Interpolation is permissible. Do not extrapolate.