PERFORMANCE DATA (cont)

FAN PERFORMANCE Ð 580D036-150 HORIZONTAL DISCHARGE UNITS (cont)

580D048 (4 TONS) Ð STANDARD MOTOR (DIRECT DRIVE)

Air¯ow

 

 

Low Speed

 

 

 

 

 

High Speed

 

 

 

 

208 v

 

 

230, 460, 575 v

 

208 v

 

 

230, 460, 575 v

(Cfm)

 

 

 

 

 

 

 

Esp

Bhp

Watts

Esp

 

Bhp

Watts

Esp

Bhp

Watts

Esp

 

Bhp

Watts

1200

0.75

0.41

458

0.81

 

0.45

506

0.87

0.51

572

0.92

 

0.56

632

1300

0.68

0.42

471

0.74

 

0.46

521

0.79

0.52

589

0.85

 

0.58

651

1400

0.60

0.45

503

0.66

 

0.49

556

0.71

0.54

616

0.77

 

0.60

681

1500

0.51

0.47

536

0.58

 

0.52

593

0.64

0.56

631

0.70

 

0.62

698

1600

0.42

0.49

557

0.49

 

0.54

616

0.56

0.58

654

0.63

 

0.64

723

1700

0.32

0.52

584

0.39

 

0.57

646

0.48

0.60

678

0.55

 

0.66

750

1800

0.21

0.54

610

0.29

 

0.60

674

0.41

0.62

698

0.48

 

0.68

772

1900

0.09

0.56

629

0.18

 

0.62

696

0.33

0.64

720

0.41

 

0.70

796

2000

Ð

Ð

Ð

0.06

 

0.65

731

0.26

0.66

744

0.33

 

0.73

823

 

 

LEGEND

Bhp

Ð Brake Horsepower Input to Fan

Esp

Ð

External Static Pressure (in. wg)

FIOP

Ð

Factory-Installed Option

NOTES:

1.Values include losses for ®lters, unit casing, and wet coils. See page 52 for accessory/FIOP static pressure information.

2.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Performance table on page 55 for addi- tional information.

3.Use of a ®eld-supplied motor may affect wire sizing. Contact your local representative for details.

580D048 (4 TONS) Ð ALTERNATE MOTOR (BELT DRIVE)*

Air¯ow

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

0.1

 

 

0.2

 

 

 

 

0.3

 

 

 

 

 

0.4

 

 

 

 

 

0.6

 

 

 

 

 

0.7

 

 

0.8

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

569

0.18

189

641

0.23

242

 

701

 

0.29

 

299

 

761

 

0.34

 

357

 

859

 

0.46

 

483

 

901

 

0.52

546

943

0.58

609

1300

604

0.22

231

673

0.28

294

 

731

 

0.34

 

352

 

788

 

0.39

 

410

 

887

 

0.52

 

546

 

928

 

0.59

615

968

0.65

683

1400

640

0.27

284

705

0.33

347

 

761

 

0.39

 

410

 

817

 

0.45

 

473

 

914

 

0.59

 

620

 

955

 

0.66

688

996

0.72

757

1500

676

0.32

336

738

0.38

399

 

793

 

0.45

 

468

 

847

 

0.51

 

536

 

940

 

0.65

 

683

 

982

 

0.73

767

1024

0.81

851

1600

713

0.38

399

772

0.44

462

 

825

 

0.51

 

536

 

877

 

0.58

 

609

 

967

 

0.73

 

767

 

1009

 

0.81

851

1051

0.89

935

1700

750

0.45

473

806

0.51

536

 

857

 

0.59

 

615

 

908

 

0.66

 

693

 

997

 

0.81

 

851

 

1037

 

0.90

940

1077

1.01

1030

1800

788

0.52

546

841

0.59

620

 

890

 

0.67

 

704

 

939

 

0.75

 

788

 

1026

 

0.91

 

956

 

1065

 

1.01

1040

1104

1.07

1124

1900

826

0.60

630

876

0.68

714

 

924

 

0.76

 

799

 

971

 

0.84

 

883

 

1056

 

1.01

 

1061

 

1094

 

1.10

1151

1132

1.18

1240

2000

864

0.70

735

912

0.77

809

 

958

 

0.86

 

898

 

1004

 

0.94

 

988

 

1087

 

1.12

 

1177

 

1125

 

1.21

1271

1162

1.30

1366

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

580D048 (4 TONS) Ð ALTERNATE MOTOR (BELT DRIVE)* (cont)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air¯ow

 

 

 

 

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

0.9

 

 

1.0

 

 

 

 

1.1

 

 

 

 

 

1.2

 

 

 

 

 

1.4

 

 

 

 

 

1.6

 

 

1.8

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1200

987

0.64

652

1030

0.70

695

 

1068

 

0.79

792

 

1106

 

0.87

 

889

 

1134

 

0.98

 

998

 

1189

 

1.12

1138

1245

1.21

1358

1300

1006

0.71

709

1044

0.77

736

 

1086

 

0.84

833

 

1128

 

0.91

 

930

 

1183

 

1.10

 

1052

 

1226

 

1.23

1215

1297

1.35

1406

1400

1033

0.79

797

1069

0.86

838

 

1104

 

0.93

925

 

1139

 

1.01

 

1012

 

1218

 

1.14

 

1090

 

1286

 

1.34

1282

1320

1.48

1463

1500

1060

0.88

891

1095

0.95

930

 

1129

 

1.02

1022

 

1162

 

1.09

 

1114

 

1228

 

1.24

 

1186

 

1303

 

1.40

1339

1343

1.60

1530

1600

1087

1.01

1001

1123

1.05

1073

 

1156

 

1.13

1150

 

1185

 

1.20

 

1226

 

1250

 

1.35

 

1291

 

1319

 

1.51

1444

1382

1.68

1607

1700

1114

1.07

1108

1151

1.15

1185

 

1183

 

1.23

1262

 

1215

 

1.31

 

1339

 

1276

 

1.48

 

1415

 

1334

 

1.64

1569

1398

1.80

1722

1800

1141

1.17

1221

1178

1.26

1318

 

1211

 

1.35

1390

 

1243

 

1.43

 

1461

 

1303

 

1.61

 

1540

 

1359

 

1.78

1702

1418

1.95

1865

1900

1168

1.28

1371

1204

1.37

1502

 

1238

 

1.47

1548

 

1271

 

1.56

 

1594

 

1330

 

1.74

 

1664

 

1386

 

1.93

1846

1439

2.11

2018

2000

1197

1.39

1485

1231

1.48

1604

 

1265

 

1.59

1666

 

1298

 

1.69

 

1727

 

1358

 

1.89

 

1808

 

1413

 

2.08

1989

1466

2.27

2171

 

 

LEGEND

Bhp

Ð Brake Horsepower Input to Fan

FIOP

Ð

Factory-Installed Option

Watts

Ð

Input Watts to Motor

*Motor drive range is 835 to 1185 rpm. All other rpms require a ®eld- supplied drive.

NOTES:

1.Boldface indicates ®eld-supplied motor and drive are required.

2.Values include losses for ®lters, unit casing, and wet coils. See page 52 for accessory/FIOP static pressure information.

3.Maximum continuous bhp is 1.00 and the maximum continuous watts are 1000. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with con®- dence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit war- ranty will not be affected. See Evaporator-Fan Motor Performance table on page 55 for additional information.

4.Use of a ®eld-supplied motor may affect wire sizing. Contact your local representative for details.

5.Interpolation is permissible. Do not extrapolate.

40

Page 40
Image 40
Bryant 580D Rpm Bhp Watts 1200 569 189 641, 299 761 357 859 483 901 546 943 609 1300 604 231 673, 695, 792, 736, 833, 1052