PHYSICAL DATA Ð 579F180-300 (cont)

UNIT SIZE 579F

180

216

 

240

300

 

LOW/HIGH HEAT

LOW/HIGH HEAT

 

LOW/HIGH HEAT

LOW/HIGH HEAT

 

 

 

 

 

FURNACE SECTION

 

 

 

 

 

 

Rollout Switch Cutout

 

 

 

 

 

 

 

Temp (F)²²

190

190

 

190

190

 

Burner Ori®ce Diameter

 

 

 

 

 

 

 

(in. ...drill size)

 

 

 

 

 

 

 

Natural Gas

0.1405...28/0.136...29

0.1405...28/0.136...29

 

0.1405...28/0.136...29

0.1405...28/0.136...29

 

Thermostat Heat Anticipator Setting (amps)

 

 

 

 

 

 

 

208/230 v Stage 1

0.98

0.98

 

0.98

0.98

 

 

Stage 2

0.44

0.44

 

0.44

0.44

 

 

460 v Stage 1

0.80

0.80

 

0.80

0.80

 

 

Stage 2

0.44

0.44

 

0.44

0.44

 

Gas Input (Btuh) Stage 1

172,000/225,000

206,000/270,000

 

206,000/270,000

206,000/270,000

 

 

Stage 2

230,000/300,000

275,000/360,000

 

275,000/360,000

275,000/360,000

 

Efficiency (Steady State) (%)

81

81

 

81

81

 

Temperature Rise Range

15-45/30-60

15-45/20-50

 

15-45/20-50

15-45/20-50

 

Manifold Pressure (in. wg)

 

 

 

 

 

 

 

Natural Gas

3.3

3.3

 

3.3

3.3

 

Gas Valve Pressure Range

 

 

 

 

 

 

 

in. wg

5.5-13.5

5.5-13.5

 

5.5-13.5

5.5-13.5

 

 

psig

0.235-0.487

0.235-0.487

 

0.235-0.487

0.235-0.487

 

Gas Valve Quantity

1

1

 

1

1

 

Field Gas Connection Size (in.)

3¤4

3¤4

 

3¤4

3¤4

 

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

Standard Compressor Internal Relief

 

 

Ð

 

 

 

(Differential)

 

 

 

 

 

 

 

Cutout

 

426

 

 

 

Reset (Auto.)

 

320

 

 

LOW-PRESSURE SWITCH (psig)

 

 

 

 

 

 

Cutout

 

 

7

 

 

Reset (Auto.)

 

22

 

 

FREEZE PROTECTION THERMOSTAT (F)

 

 

 

 

 

 

Opens

 

30 ± 5

 

 

Closes

 

45 ± 5

 

 

OUTDOOR-AIR INLET SCREENS

 

Cleanable

 

 

Quantity...Size (in.)

 

2...20 x 25 x 1

 

 

 

 

 

1...20 x 20 x 1

 

 

RETURN-AIR FILTERS

 

Throwaway

 

 

Quantity...Size (in.)

 

4...20 x 20 x 2

 

 

 

 

 

4...16 x 20 x 2

 

 

POWER EXHAUST

1¤2 Hp 208/230-460 v Motor Direct Drive, Prop-Fan (Factory-wired for 460 v)

 

 

LEGEND

 

²²Rollout switch lockout is manually reset by interrupting power to unit

Al

Ð Aluminum

 

or resetting thermostat.

 

 

Bhp

Ð Brake Horsepower

 

The 579F300 unit requires 2-in. industrial-grade ®lters capable of

Cu

Ð Copper

 

handling face velocities of up to 625 ft/min (such as American Air Fil-

TXV Ð Thermostatic Expansion Valve

 

ter no. 5700 or equivalent).

 

 

*Evaporator coil ®n material/condenser coil ®n material.

NOTE: The 579F180-300 units have a low-pressure switch (standard)

²Weight of 14-in. roof curb.

 

located on the suction side.

 

 

**On 579F180-300 units, Circuit 1 consists of lower portion of con- denser coil and lower portion of evaporator coil, and Circuit 2 is the upper portion of both coils.