Bryant PHYSICAL DATA Ð 580D090-150, OPERATING WEIGHT lb, Compressor, Hermetic, R-22, Fins

Models: 580D

1 72
Download 72 pages 58.37 Kb
Page 10
Image 10
PHYSICAL DATA Ð 580D090-150

PHYSICAL DATA Ð 580D090-150

UNIT SIZE 580D

 

090

102

 

120

150

NOMINAL CAPACITY (tons)

 

71¤2

81¤2

 

10

121¤2

OPERATING WEIGHT (lb)

 

 

 

 

 

 

Unit

 

 

 

 

 

 

Al/Al*

 

870

880

 

1035

1050

Al/Cu*

 

881

896

 

1057

1077

Cu/Cu*

 

893

907

 

1080

1100

Economizer

 

 

 

 

 

 

Durablade

 

44

44

 

44

44

Parablade

 

62

62

 

62

62

Roof Curb²

 

143

143

 

143

143

COMPRESSOR

 

 

Hermetic

 

Quantity

 

2

2

2

2

No. Cylinders (per Circuit)

 

2

2

2

2

Oil (oz)

 

50 ea

50 ea

 

50 ea

54 ea

REFRIGERANT TYPE

 

 

 

R-22

 

Expansion Device

 

 

Acutrol™ Feed Device

 

Operating Charge (lb-oz)

 

 

 

 

 

 

Circuit 1

 

4-13

6-14

 

5-13

8-10

Circuit 2

 

4-14

6- 3

 

5-14

8- 8

CONDENSER COIL

 

Enhanced Copper Tubes,

Aluminum Lanced

Fins

Rows...Fins/in.

 

1...17

2...17

 

2...17

2...17

Total Face Area (sq ft)

 

20.50

18.00

 

17.42

25.00

CONDENSER FAN

 

 

Propeller

Type

 

Nominal Cfm

 

6500

6500

 

7000

7000

Quantity...Diameter (in.)

 

2...22

2...22

 

2...22

2...22

Motor Hp...Rpm

 

1¤4...1100

1¤4...1100

 

1¤4...1100

1¤4...1100

Watts Input (Total)

 

600

600

 

600

600

EVAPORATOR COIL

 

Enhanced Copper Tubes,

Aluminum Double-Wavy Fins

Rows...Fins/in.

 

3...15

3...15

 

3...15

4...15

Total Face Area (sq ft)

 

8.0

8.0

 

10.0

11.1

EVAPORATOR FAN

 

 

Centrifugal

Type

 

Quantity...Size (in.)

Std

1...15 x 15

1...15 x 15

 

1...15 x 15

1...15 x 15

 

Alt

1...15 x 15

Ð

 

1...15 x 15

1...15 x 15

Type Drive

Std

Belt

Belt

 

Belt

Belt

Nominal Cfm

Alt

Belt

Ð

 

Belt

Belt

 

3000

3400

 

4000

5000

Motor Hp

Std

Ð

Ð

 

Ð

Ð

 

Alt

Ð

Ð

 

Ð

Ð

Maximum Continuous Bhp

Std

2.40

2.40

 

2.40

4.20

 

Alt

Ð

Ð

 

2.90

5.25

Motor Frame Size

Std

56

56

 

56

56

Nominal Rpm High/Low

Alt

Ð

Ð

 

56

56

 

Ð

Ð

 

Ð

Ð

Fan Rpm Range

Std

590-840

685-935

 

685-935

860-1080

Motor Bearing Type

Alt

685-935

Ð

 

835-1085

900-1260

 

Ball

Ball

 

Ball

Ball

Maximum Allowable Rpm

 

2100

2100

 

2100

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.4/3.4

2.8/3.8

 

2.8/3.8

4.0/5.0

 

Alt

2.8/3.8

Ð

 

3.4/4.4

3.1/4.1

Nominal Motor Shaft Diameter (in.)

Std

5¤8

5¤8

 

5¤8

7¤8

 

Alt

Ð

Ð

 

7¤8

7¤8

Fan Pulley Pitch Diameter (in.)

Std

7.0

7.0

 

7.0

8.0

Nominal Fan Shaft Diameter (in.)

Alt

7.0

Ð

 

7.0

5.9

 

Ð

Ð

 

Ð

Ð

Belt, Quantity...Type...Length (in.)

Std

1...A...49

1...A...49

 

1...A...49

1...A...52

 

Alt

1...A...49

Ð

 

1...A...49

1...BX...46

Pulley Center Line Distance (in.)

Std

16.75-19.25

16.75-19.25

 

15.85-17.50

15.85-17.50

 

Alt

16.75-19.25

Ð

 

15.85-17.50

15.85-17.50

Speed Change per Full Turn of

Std

50

50

 

50

44

Movable Pulley Flange (rpm)

Alt

50

Ð

 

50

50

Movable Pulley Maximum Full Turns

Std

5

5

 

5

5

From Closed Position

Alt

5

Ð

 

5

6

Factory Setting

Std

5

5

 

5

5

 

Alt

5

Ð

 

5

5

Factory Speed Setting (rpm)

Std

590

685

 

685

860

Fan Shaft Diameter at Pulley (in.)

Alt

685

Ð

 

835

960

 

1

1

 

1

1

 

LEGEND

Al

Ð Aluminum

Bhp

Ð Brake Horsepower

Cu

Ð Copper

*Evaporator coil ®n material/condenser coil ®n material. Contact your local representative for details about coated ®ns.

²Weight of 14-in. roof curb.

**Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat.

²²Requires an optional or accessory Controls Upgrade Kit.

NOTE: The 580D036-150 units have a loss-of-charge/low-pressure switch (accessory or option) located in the liquid line.

10

Page 10
Image 10
Bryant PHYSICAL DATA Ð 580D090-150, OPERATING WEIGHT lb, Compressor, Hermetic, Refrigerant Type, R-22, Condenser Coil