prodUCt speCifiCations prodUCt speCifiCations
14 www.goodmanmfg.com SS-CPC90-150
heat kit eleCtriCal data (Blower only, heat mode) — 10 tons

kw CorreCtion faCtor

kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage 240 230 220 210 208
Correcon Factor 1 0.93 0.82 0.78 0.76
kW Correction Factor for 480V Units
Actual Voltage 460 440 430
Correcon Factor 0.92 0.84 0.8
For other voltage use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage 560 550 540
Correcon Factor 0.95 0.91 0.88
Multiply rated kW by correction factor to get actual kW
minimUm airflow for eleCtriC heat
Heater Size (kW) Min. CFM
Down-shot
Min. CFM
Horizontal
15 4,000 4,000
30 4,000 4,000
43 4,000 4,000
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC120XXX3BXXX 49 60
EHK3-16 48 / 55 50 / 60 15 3500 - 4500 CFM
EHK3-30 87 / 100 90 / 100 30 3500 - 4500 CFM
EHK3-45 121 / 139 125 / 150 43 4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC120XXX3HXXX 50 60
EHK3-16 49 / 57 50 / 60 15 3500 - 4500 CFM
EHK3-30 88 / 102 90 / 110 30 3500 - 4500 CFM
EHK3-45 122 / 141 125 / 150 43 4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPC120XXX4BXXX 24 30
EHK4-16 27 30 15 3500 - 4500 CFM
EHK4-30 50 50 30 3500 - 4500 CFM
EHK4-45 70 70 43 4000 - 4500 CFM
Model and
Heat Kit Usage

MCA¹

at 575V

MOP² (amps)

at 575V

Actual kW

at 575V
Recommended
Airflow Range
CPC0120XXX7BXXX 17 20
EHK7-16 22 25 15 3500 - 4500 CFM
EHK7-30 41 45 30 3500 - 4500 CFM
EHK7-45 57 60 43 4000 - 4500 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon device