Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode) — 10 Tons

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 208 / 240V

at 208 / 240V

at 240V

Airflow Range

 

 

 

 

 

CPC120XXX3BXXX

49

60

 

 

EHK3-16

48 / 55

50 / 60

15

3500 - 4500 CFM

EHK3-30

87 / 100

90 / 100

30

3500 - 4500 CFM

EHK3-45

121 / 139

125 / 150

43

4000 - 4500 CFM

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 208 / 240V

at 208 / 240V

at 240V

Airflow Range

 

 

 

 

 

CPC120XXX3HXXX

50

60

 

 

EHK3-16

49 / 57

50 / 60

15

3500 - 4500 CFM

EHK3-30

88 / 102

90 / 110

30

3500 - 4500 CFM

EHK3-45

122 / 141

125 / 150

43

4000 - 4500 CFM

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 480V

at 480V

at 480V

Airflow Range

 

 

 

 

 

CPC120XXX4BXXX

24

30

 

 

EHK4-16

27

30

15

3500 - 4500 CFM

EHK4-30

50

50

30

3500 - 4500 CFM

EHK4-45

70

70

43

4000 - 4500 CFM

 

 

 

 

 

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 575V

at 575V

at 575V

Airflow Range

 

 

 

 

 

CPC0120XXX7BXXX

17

20

 

 

EHK7-16

22

25

15

3500 - 4500 CFM

EHK7-30

41

45

30

3500 - 4500 CFM

EHK7-45

57

60

43

4000 - 4500 CFM

 

 

 

 

 

¹ Minimum Circuit Ampacity

 

 

 

 

² Maximum Overcurrent Protection device

kW Correction Factor

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

220

210

208

 

 

 

 

 

 

Correction Factor

1

0.93

0.82

0.78

0.76

 

 

 

 

 

 

kW Correction Factor for 480V Units

 

 

 

 

 

 

Actual Voltage

460

440

 

430

 

 

 

 

 

Correction Factor

0.92

0.84

 

0.8

 

 

 

 

 

For other voltage use voltage² / 480²

 

 

 

 

 

kW Correction Factor for 575V Units

 

 

 

 

 

 

Supply Voltage

560

550

 

540

 

 

 

 

 

Correction Factor

0.95

0.91

 

0.88

 

 

 

 

 

Multiply rated kW by correction factor to get actual kW

Minimum Airflow for Electric Heat

Heater Size (kW)

Min. CFM

Min. CFM

Down-shot

Horizontal

 

 

 

 

15

4,000

4,000

 

 

 

30

4,000

4,000

 

 

 

43

4,000

4,000

 

 

 

14

www.goodmanmfg.com

SS-CPC90-150

Page 14
Image 14