Product Specifications
Product Specifications — 8½ Tons
CPC102
XXX3BXXX
CPC102
XXX4BXXX
CPC102
XXX7BXXX
Cooling Capacity
Total, BTU/h
Sensible BTU/h
EER / IEER
Decibels
ARI Reference #s
| 102,000 | 102,000 | 102,000 | 
| 70,380 | 70,380 | 70,380 | 
| 11.3 / 11.2 | 11.3 / 11.2 | 11.3 / 11.2 | 
| 83 | 83 | 83 | 
| 3620220 | 3620220 | 3620220 | 
| 
 | 
 | 
 | 
Evapoartor Motor / Coil
| Motor Type | Belt Drive | Belt Drive | Belt Drive | 
| 
 | 
 | 
 | 
 | 
| Indoor Nominal CFM | 3,400 | 3,400 | 3,400 | 
| 
 | 
 | 
 | 
 | 
| Indoor Motor FLA (Cooling) | 7.8 | 3.9 | 2.3 | 
| 
 | 
 | 
 | 
 | 
| Horsepower - RPM | 1725 | 1725 | 1725 | 
| 
 | 
 | 
 | 
 | 
| Piston Size (Cooling) | 0.08 | 0.08 | 0.08 | 
| 
 | 
 | 
 | 
 | 
| Filter Size (Qty) | (4) 16” x 20” x 2” | (4) 16” x 20” x 2” | (4) 16” x 20” x 2” | 
| 
 | 
 | 
 | 
 | 
| Drain Size (NPT) | 3/4" | 3/4" | 3/4" | 
| 
 | 
 | 
 | 
 | 
| 180 oz. | 180 oz. | 180 oz. | |
| 
 | 
 | 
 | 
 | 
| Evaporator Coil Face Area (ft2) | 8.9 | 8.9 | 8.9 | 
| 
 | 
 | 
 | 
 | 
| Rows Deep / Fins per Inch | 4 / 16 | 4 / 16 | 4 / 16 | 
| 
 | 
 | 
 | 
 | 
| Belt Drive Evap Fan Data | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
| # of Wheels (D x W) | 1 (15" x 12") | 1 (15" x 12") | 1 (15" x 12") | 
| 
 | 
 | 
 | 
 | 
| Motor Sheave / Blower Sheave | VL40 / AK74 | VL40 / AK74 | VL40 / AK74 | 
| 
 | 
 | 
 | 
 | 
| Belt | AX51 | AX51 | AX51 | 
| 
 | 
 | 
 | 
 | 
| Condenser Fan / Coil | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
| Quantity of Condenser Fan Motors | 2 | 2 | 2 | 
| 
 | 
 | 
 | 
 | 
| Horsepower - RPM | 1/4" - 1,090 | 1/4" - 890 | 1/4" - 1,075 | 
| 
 | 
 | 
 | 
 | 
| Fan Diameter / # Fan Blades | 22 / 4 | 22 / 4 | 22 / 4 | 
| 
 | 
 | 
 | 
 | 
| Outdoor Nominal CFM | 7,600 | 7,600 | 7,600 | 
| 
 | 
 | 
 | 
 | 
| Face Area (ft2) | 13.25 | 13.25 | 13.25 | 
| 
 | 
 | 
 | 
 | 
| Rows Deep / Fins per Inch | 2 / 22 | 2 / 22 | 2 / 22 | 
| 
 | 
 | 
 | 
 | 
| Compressor | 
 | 
 | 
 | 
Quantity / Type
Stage
| 2 / Scroll | 2 / Scroll | 2 / Scroll | 
| 1 | 1 | 1 | 
| 
 | 
 | 
 | 
Electrical Data / Static
| Voltage / Phase / Frequency | 230 / 3 / 60 | 460 / 3 / 60 | 575 / 3 / 60 | 
| 
 | 
 | 
 | 
 | 
| Quantity of Compressors | 2 | 2 | 2 | 
| 
 | 
 | 
 | 
 | 
| Compressor RLA / LRA ea. | 14.5 / 98 | 6.3 / 55 | 6.0 / 41 | 
| 
 | 
 | 
 | 
 | 
| Standard Max Static | 1" | 1 | 1 | 
| 
 | 
 | 
 | 
 | 
| Outdoor Fan FLA ea. | 1.4 | 0.8 | 0.6 | 
| 
 | 
 | 
 | 
 | 
| Total Unit Amps | 39.6 | 18.1 | 15.5 | 
| 
 | 
 | 
 | 
 | 
| Min. Circuit Ampacity¹ | 43.2 | 19.7 | 17 | 
| 
 | 
 | 
 | 
 | 
| Max. Overcurrent Protection (amps)² | 50 | 25 | 20 | 
| 
 | 
 | 
 | 
 | 
| Entrance Power Supply | Locating | Locating | Locating | 
| Entrance Control Voltage | Dimple | Dimple | Dimple | 
| 
 | 
 | 
 | 
 | 
| Operating Weight (lbs) | 975 | 975 | 975 | 
| 
 | 
 | 
 | 
 | 
| Ship Weight (lbs) | 1000 | 1000 | 1000 | 
| 
 | 
 | 
 | 
 | 
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or 
Note: Always check the S&R plate for electrical data on the unit being installed.
| 4 | www.goodmanmfg.com | 