Product Specifications
Product Specifications — 10 Tons
CPC120
XXX3BXXX
CPC120
XXX4BXXX
CPC120
XXX7BXXX
Cooling Capacity
Total BTU/h
Sensible BTU/h
EER / IEER
Decibels
ARI Reference #s
| 118,000 | 118,000 | 118,000 | 
| 87,300 | 87,300 | 87,300 | 
| 11.5 / 11.2 | 11.5 / 11.2 | 11.5 / 11.2 | 
| 83.0 | 83.0 | 83.0 | 
| 3023833 | 3023833 | 3023833 | 
| 
 | 
 | 
 | 
Evaporator Motor / Coil
| Motor Type | Belt Drive | Belt Drive | Belt Drive | 
| 
 | 
 | 
 | 
 | 
| Indoor Nominal CFM | 4,000 | 4,000 | 4,000 | 
| 
 | 
 | 
 | 
 | 
| Indoor motor FLA (Cooling) | 7.8 | 3.9 | 2.7 | 
| 
 | 
 | 
 | 
 | 
| Horsepower - RPM | 2.0/1725 | 2.0/1725 | 2.0/1725 | 
| 
 | 
 | 
 | 
 | 
| Piston Size (Cooling) | 0.086 | 0.086 | 0.086 | 
| 
 | 
 | 
 | 
 | 
| Filter Size (Qty) | (4) 16” x 24” x 2” | (4) 16” x 24” x 2” | (4) 16” x 24” x 2” | 
| 
 | 
 | 
 | 
 | 
| Drain Size (NPT) | ¾” | ¾” | ¾” | 
| 
 | 
 | 
 | 
 | 
| 220 oz. | 220 oz. | 220 oz. | |
| 
 | 
 | 
 | 
 | 
| Evaporator Coil Face Area (ft²) | 10.2 | 10.2 | 10.2 | 
| 
 | 
 | 
 | 
 | 
| Rows Deep / Fins per Inch | 4 / 14 | 4 / 14 | 4 / 14 | 
| 
 | 
 | 
 | 
 | 
| Belt Drive Evap Fan Data | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
| # of Wheels (D x W) | (1) 15” x 15” | (1) 15” x 15” | (1) 15” x 15” | 
| 
 | 
 | 
 | 
 | 
| Motor Sheave / Blower Sheave | VL40 / AK74 | VL40 / AK74 | VL40 / AK74 | 
| 
 | 
 | 
 | 
 | 
| Belt | AX51 | AX51 | AX51 | 
| 
 | 
 | 
 | 
 | 
| Condenser Fan / Coil | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
| Quantity of Condenser Fan Motors | 2 | 2 | 2 | 
| 
 | 
 | 
 | 
 | 
| Horsepower - RPM | ⅓ - 1,075 | ⅓ - 1,075 | ⅓ - 1,075 | 
| 
 | 
 | 
 | 
 | 
| Fan Diameter / # Fan Blades | 22 / 3 | 22 / 3 | 22 / 3 | 
| 
 | 
 | 
 | 
 | 
| Outdoor Nominal CFM | 7,200 | 7,200 | 7,200 | 
| 
 | 
 | 
 | 
 | 
| Face Area (ft²) | 32.4 | 32.4 | 32.4 | 
| 
 | 
 | 
 | 
 | 
| Rows Deep - Fins per Inch | 2/2 rows - 22 fpi | 2/2 rows - 22 fpi | 2/2 rows - 22 fpi | 
| 
 | 
 | 
 | 
 | 
| Compressor | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
Quantity / Type
Stage
Electrical Data
| 2 / Scroll | 2 / Scroll | 2 / Scroll | 
| 1 | 1 | 1 | 
| Voltage/Phase/ Frequency | 460/3/60 | 575/3/60 | |
| 
 | 
 | 
 | 
 | 
| Quantity of Compressors | 2 | 2 | 2 | 
| 
 | 
 | 
 | 
 | 
| Compressor RLA / LRA ea. | 16/110.0 | 7.8/52.0 | 5.7/38.9 | 
| 
 | 
 | 
 | 
 | 
| Standard Max Static | 2.0” | 2.0” | 2.0” | 
| 
 | 
 | 
 | 
 | 
| Outdoor Fan RLA ea. | 2.40 | 1.20 | 0.89 | 
| 
 | 
 | 
 | 
 | 
| Total Unit Amps | 45 | 22 | 16 | 
| 
 | 
 | 
 | 
 | 
| Min. Circuit Ampacity¹ | 49 | 24 | 17 | 
| 
 | 
 | 
 | 
 | 
| Max. Overcurrent Protection (amps)² | 60.0 | 30 | 20 | 
| 
 | 
 | 
 | 
 | 
| Entrance Power Supply | Locating | Locating | Locating | 
| Entrance Control Voltage | Dimple | Dimple | Dimple | 
| 
 | 
 | 
 | 
 | 
| Operating Weight (lbs) | 1135 | 1135 | 1135 | 
| 
 | 
 | 
 | 
 | 
| Ship Weight (lbs) | 1175 | 1175 | 1175 | 
| 
 | 
 | 
 | 
 | 
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or 
Note: Always check the S&R plate for electrical data on the unit being installed.
| www.goodmanmfg.com | 5 | 