Product Specifications
Product Specifications — 7½ Tons
| A Models |
| B Models |
| |
|
|
| |||
|
|
|
|
|
|
| CPC090 | CPC090 | CPC090 | CPC090 | CPC090 |
| XXX3BXXX | XXX4BXXX | XXX3BXXX | XXX4BXXX | XXX7BXXX |
|
|
|
|
|
|
Cooling Capacity |
|
|
|
|
|
|
|
|
|
|
|
Total BTU/h | 90,000 | 90,000 | 90,000 | 90,000 | 90,000 |
|
|
|
|
|
|
Sensible BTU/h | 65,700 | 65,700 | 64,000 | 64,000 | 64,000 |
|
|
|
|
|
|
EER / IEER | 11.5 / 11.5 | 11.5 / 11.5 | 11.5 / 11.5 | 11.5 / 11.5 | 11.5 / 11.5 |
Decibels | 82.0 | 82.0 | 82.0 | 82.0 | 82.0 |
|
|
|
|
|
|
AHRI Reference #s | 3000986 | 3000986 | 3620223 | 3620223 | 3620223 |
|
|
|
|
|
|
Evaporator Motor / Coil |
|
|
|
|
|
|
|
|
|
|
|
Motor Type | Belt Drive | Belt Drive | Belt Drive | Belt Drive | Belt Drive |
|
|
|
|
|
|
Indoor Nominal CFM | 3,000 | 3,000 | 3,000 | 3,000 | 3,000 |
Indoor Motor FLA (Cooling) | 7.8 | 3.9 | 5.0 | 2.5 | 2.3 |
|
|
|
|
|
|
Horsepower / RPM | 2.0 / 1725 | 2.0 / 1725 | 1.5 / 1745 | 1.5 / 1745 | 1.5 / 1725 |
|
|
|
|
|
|
Piston Size (Cooling) | 0.076 | 0.076 | 0.078 | 0.078 | 0.078 |
|
|
|
|
|
|
Filter Size (Qty) | (4) 16”x24”x2” | (4) 16”x24”x2” | (4) 16”x20”x2” | (4) 16”x20”x2” | (4) 16”x20”x2” |
|
|
|
|
|
|
Drain Size (NPT) | ¾” | ¾” | ¾” | ¾” | ¾” |
215 oz. | 215 oz. | 175 oz. | 175 oz. | 175 oz. | |
|
|
|
|
|
|
Evaporator Coil Face Area (ft²) | 10.2 | 10.2 | 8.9 | 8.9 | 8.9 |
|
|
|
|
|
|
Rows Deep / Fins per Inch | 4 / 16 | 4 / 16 | 4 / 16 | 4 / 16 | 4 / 16 |
|
|
|
|
|
|
Belt Drive Evap Fan Data |
|
|
|
|
|
|
|
|
|
|
|
# of Wheels (D x W) | 1 (15” x 12”) | 1 (15” x 12”) | 1 (15” x 12”) | 1 (15” x 12”) | 1 (15” x 12”) |
Motor Sheave / Blower Sheave | VL40 / AK74 | VL40 / AK74 | VL40 / AK74 | VL40 / AK74 | VL40 / AK74 |
|
|
|
|
|
|
Belt | AX51 | AX51 | AX51 | AX51 | AX51 |
|
|
|
|
|
|
Condenser Fan / Coil |
|
|
|
|
|
|
|
|
|
|
|
Quantity of Condenser Fan Motors | 2 | 2 | 2 | 2 | 2 |
|
|
|
|
|
|
Horsepower - RPM | ¼ - 1090 | ¼ - 890 | ¼ - 1075 | ¼ - 890 | ¼ - 1,075 |
Fan Diameter / # Fan Blades | 22 / 4 | 22 / 4 | 22 / 4 | 22 / 4 | 22 / 4 |
|
|
|
|
|
|
Outdoor Nominal CFM | 7,600 | 7,600 | 7,600 | 7,600 | 7,600 |
|
|
|
|
|
|
Face Area (ft²) | 32.4 | 32.4 | 26.5 | 26.5 | 26.5 |
|
|
|
|
|
|
Rows Deep / Fins per Inch | 2 / 20 | 2 / 20 | 2 / 22 | 2 / 22 | 2 / 22 |
|
|
|
|
|
|
Compressor |
|
|
|
|
|
Quantity / Type | 2 / Scroll | 2 / Scroll | 2 / Scroll | 2 / Scroll | 2 / Scroll |
|
|
|
|
|
|
Stage | 1 | 1 | 1 | 1 | 1 |
|
|
|
|
|
|
Electrical Data |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Quantity of Compressors | 2 | 2 | 2 | 2 | 2 |
Compressor RLA / LRA | 13.1 / 83.1 | 6.1 / 41.0 | 13.1 / 83.1 | 6.1 / 41.0 | 4.4 / 33.0 |
|
|
|
|
|
|
Max External Static | 1.5” | 1.5” | 1.0” | 1.0” | 1.0” |
|
|
|
|
|
|
Outdoor Fan HP / RLA | (2) ¼ / 1.4 | (2) ¼ / 0.8 | (2) ¼ / 1.4 | (2) ¼ / 0.8 | (2) ¼ / 0.6 |
|
|
|
|
|
|
Total Unit Amps | 36.9 | 17.7 | 34.0 | 16.3 | 12.3 |
|
|
|
|
|
|
Min. Circuit Ampacity¹ | 40 | 19 | 37.3 | 17.8 | 13.4 |
Max. Overcurrent Protection (amps)² | 50 | 25 | 50 | 20 | 15 |
|
|
|
|
|
|
Entrance Power Supply | Locating | Locating | Locating | Locating | Locating |
Entrance Control Voltage | Dimple | Dimple | Dimple | Dimple | Dimple |
|
|
|
|
|
|
Operating Weight (lbs) | 1110 | 1110 | 975 | 975 | 975 |
|
|
|
|
|
|
Ship Weight (lbs) | 1150 | 1150 | 1000 | 1000 | 1000 |
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.
www.goodmanmfg.com | 3 |