prodUCt speCifiCations prodUCt speCifiCations
6 www.goodmanmfg.com SS-CPC90-150
prodUCt speCifiCations — 12½ tonsCPC150XXX
3BXXX
CPC150XXX
4BXXX
CPC150XXX
7BXXX
Cooling Capacity
Total, BTU/h 146,000 146,000 146,000
Sensible BTU/h 102,200 102,200 102,200
EER / IPLV 11.0 / 11.2 11.0 / 11.2 11.0 / 11.2
Decibels 83 83 83
ARI Reference #s 3542680 3542680 3542680
Evapoartor Motor / Coil
Motor Type Belt Drive Belt Drive Belt Drive
Indoor Nominal CFM 5,000 5,000 5,000
Indoor Motor FLA (Cooling) 9.4 4.7 4.2
Horsepower - RPM 3.0 - 1,725 3.0 - 1,725 3.0 - 1,725
Piston Size (Cooling) 0.096 0.096 0.096
Filter Size (4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2"
Drain Size (NPT) ¾" ¾" ¾"
R-410A Refrigerant Charge Cir #1 & #2 285 oz. 285 oz. 285 oz.
Evaporator Coil Face Area (2) 14.7 14.7 14.7
Rows Deep / Fins per Inch 4 / 15 4 / 15 4 / 15
Condenser Fan / Coil
Quanty of condenser Fan Motors 222
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter / # Fan Blades 22/3 22/3 22/3
Outdoor Nominal CFM 7,200 7,200 7,200
Face Area (2) 35.3 35.3 35.3
Rows Deep / Fins per Inch 2/3 rows 15 fpi 2/3 rows 15 fpi 2/3 rows 15 fpi
Belt Drive Evap Fan Data
# of Wheels (D x W) (1) 15" x 15" (1) 15" x 15" (1) 15" x 15"
Motor Sheave / Blower Sheave VL40 / AK66 VL40 / AK66 VL40 / AK66
Belt AX49 AX49 AX49
Compressor
Quanty / Type 1 / Scroll 1 / Scroll 1 / Scroll
Stage Single Single Single
Compressor RLA / LRA ea. 22.4 / 149 10.6 / 75 7.7 / 54
Electrical Data / Static
Voltage / Phase / Frequency 208-230/3/60 460/3/60 575/3/60
Outdoor Fan FLA ea. 2.4 1.2 0.9
Total Unit Amps 59 28 21.4
Min. Circuit Ampacity165 31 23
Max. Overcurrent Protecon (amps)280 40 30
Entrance Power Supply Locang
Dimple
Locang
Dimple
Locang
Dimple
Entrance Control Voltage
Operating Weight (lbs) 1275 1275 1275
Ship Weight (lbs) 1300 1300 1300
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.