prodUCt speCifiCations prodUCt speCifiCations
SS-CPC90-150 www.goodmanmfg.com 15
heat kit eleCtriCal data (Blower only, heat mode) — 12½ tons
kw CorreCtion faCtors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage 240 230 220 210 208
Correction Factor 1 0.93 0.82 0.78 0.76
kW Correction Factor (for 480V Units)
Supply Voltage 460 440 430
Correction Factor 0.92 0.84 0.8
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage 560 550 540
Correction Factor 0.95 0.91 0.88
Multiply rated kW by correction factor to get actual kW.
Model and
Heat Kit Usage
MCA1 at
208 / 240V
MOP2 (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC150***3B*** 65 80
EHK3-16 65 80 15 4000 - 5600
EHK3-30 102 110 30 4300 - 5600
EHK3-45 141 150 43 4500 - 5600
Model and
Heat Kit Usage
MCA1 at
208 / 240V
MOP2 (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC150***4B*** 31 40
EHK4-16 31 40 15 4000 - 5600
EHK4-30 51 60 30 4300 - 5600
EHK4-45 71 80 43 4500 - 5600
Model and
Heat Kit Usage
MCA1 at
208 / 240V
MOP2 (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC150***7B*** 23 30
EHK7-16 24 30 15 4000 - 5600
EHK7-30 43 45 30 4300 - 5600
EHK7-45 59 60 43 4500 - 5600
¹ Minimum Circuit Ampacity (standard drive)
² Maximum Overcurrent Protecon device (standard drive)