Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode) — 7½ Tons (A Modles)

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 208 / 240V

at 208 / 240V

at 240V

Airflow Range

 

 

 

 

 

CPC090XXX3BXXX

40

50

 

 

EHK3-16

48 / 55

50 / 60

15

3000 - 3375 CFM

EHK3-30

87 / 100

90 / 100

30

3000 - 3375 CFM

EHK3-45

121 / 139

125 / 150

43

3000 - 3375 CFM

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 480V

at 480V

at 480V

Airflow Range

 

 

 

 

 

CPC090XXX4BXXX

19

25

 

 

EHK4-16

27

30

15

3000 - 3375 CFM

EHK4-30

50

50

30

3000 - 3375 CFM

EHK4-45

70

70

43

3000 - 3375 CFM

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 575V

at 575V

at 575V

Airflow Range

 

 

 

 

 

CPC090XXX7BXXX

14

15

 

 

EHK7-16

22

25

15

---

EHK7-30

41

45

30

---

EHK7-45

57

60

43

---

 

 

 

 

 

¹ Minimum Circuit Ampacity

 

 

 

 

² Maximum Overcurrent Protection device

KW Correction Factors

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

 

220

210

208

 

 

 

 

 

 

 

Correction Factor

1

0.93

 

0.82

0.78

0.76

 

 

 

 

 

 

 

 

 

 

 

kW Correction Factor (for 480V Units)

 

 

 

 

 

 

 

 

 

 

Supply Voltage

460

440

 

430

 

 

 

 

 

 

 

 

 

Correction Factor

0.92

0.84

 

0.8

 

 

 

 

 

 

 

 

 

For other voltage, use voltage² / 480²

 

 

 

 

 

 

 

 

 

kW Correction Factor (for 575V Units)

 

 

 

 

 

 

 

 

 

 

Supply Voltage

560

550

 

540

 

 

 

 

 

 

 

 

 

Correction Factor

0.95

0.91

 

0.88

 

 

 

 

 

 

 

 

 

Multiply rated kW by correction factor to get actual kW.

Minimum Airflow for Electric Heat

Heater Size (kW)

Minimum CFM

 

 

15

3,000

 

 

30

3,000

 

 

43

3,000

 

 

SS-CPC90-150

www.goodmanmfg.com

11

Page 11
Image 11
Goodman Mfg SS-CPC90-150 Model, KW Correction Factor for 1- & 3-Phase Units Supply Voltage, Heater Size kW Minimum CFM