prodUCt speCifiCations prodUCt speCifiCations
12 www.goodmanmfg.com SS-CPC90-150
heat kit eleCtriCal data (Blower only, heat mode) — 7½ tons (B modles)
minimUm airflow for eleCtriC heat
Heater Size (kW) Minimum CFM
15 3,000
30 3,000
43 3,000
kw CorreCtion faCtors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage 240 230 220 210 208
Correction Factor 1 0.93 0.82 0.78 0.76
kW Correction Factor (for 480V Units)
Supply Voltage 460 440 430
Correction Factor 0.92 0.84 0.8
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage 560 550 540
Correction Factor 0.95 0.91 0.88
Multiply rated kW by correction factor to get actual kW.
Model and
Heat Kit Usage
MCA¹
at 240V
MOP² (amps)
at 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC090XXX3BXXX 37 50
EHK3-16 51 60 15 3000 - 3375 CFM
EHK3-30 97 100 30 3000 - 3375 CFM
EHK3-45 136 150 43 3000 - 3375 CFM
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPC090XXX4BXXX 18 20
EHK4-16 26 30 15 3000 - 3375 CFM
EHK4-30 48 50 30 3000 - 3375 CFM
EHK4-45 68 70 43 3000 - 3375 CFM
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
CPC090XXX7BXXX 13 15
EHK7-16 22 25 15 3000 - 3375 CFM
EHK7-30 41 45 30 3000 - 3375 CFM
EHK7-45 57 60 43 3000 - 3375 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon device