Product Specifications
Heat Kit Electrical Data (Blower Only, Heat Mode) — 7½ Tons (B Modles)
| Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended | 
| Heat Kit Usage | at 240V | at 240V | at 240V | Airflow Range | 
| 
 | 
 | 
 | 
 | 
 | 
| CPC090XXX3BXXX | 37 | 50 | 
 | 
 | 
| 
 | 51 | 60 | 15 | 3000 - 3375 CFM | 
| 
 | 97 | 100 | 30 | 3000 - 3375 CFM | 
| 
 | 136 | 150 | 43 | 3000 - 3375 CFM | 
| 
 | 
 | 
 | 
 | 
 | 
| Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended | 
| Heat Kit Usage | at 480V | at 480V | at 480V | Airflow Range | 
| 
 | 
 | 
 | 
 | 
 | 
| CPC090XXX4BXXX | 18 | 20 | 
 | 
 | 
| 26 | 30 | 15 | 3000 - 3375 CFM | |
| 48 | 50 | 30 | 3000 - 3375 CFM | |
| 68 | 70 | 43 | 3000 - 3375 CFM | |
| 
 | 
 | 
 | 
 | 
 | 
| Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended | 
| Heat Kit Usage | at 575V | at 575V | at 575V | Airflow Range | 
| 
 | 
 | 
 | 
 | 
 | 
| CPC090XXX7BXXX | 13 | 15 | 
 | 
 | 
| 22 | 25 | 15 | 3000 - 3375 CFM | |
| 41 | 45 | 30 | 3000 - 3375 CFM | |
| 57 | 60 | 43 | 3000 - 3375 CFM | |
| 
 | 
 | 
 | 
 | 
 | 
| ¹ Minimum Circuit Ampacity | 
 | 
 | 
 | 
 | 
² Maximum Overcurrent Protection device
KW Correction Factors
kW Correction Factor (for 1- & 3-Phase  Units)
| Supply Voltage | 240 | 230 | 
 | 220 | 210 | 208 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Correction Factor | 1 | 0.93 | 
 | 0.82 | 0.78 | 0.76 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | |||
| kW Correction Factor (for 480V Units) | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Supply Voltage | 460 | 440 | 
 | 430 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Correction Factor | 0.92 | 0.84 | 
 | 0.8 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| For other voltage, use voltage² / 480² | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | |||
| kW Correction Factor (for 575V Units) | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Supply Voltage | 560 | 550 | 
 | 540 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Correction Factor | 0.95 | 0.91 | 
 | 0.88 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
Multiply rated kW by correction factor to get actual kW.
Minimum Airflow for Electric Heat
| Heater Size (kW) | Minimum CFM | 
| 
 | 
 | 
| 15 | 3,000 | 
| 
 | 
 | 
| 30 | 3,000 | 
| 
 | 
 | 
| 43 | 3,000 | 
| 
 | 
 | 
| 12 | www.goodmanmfg.com | 