Product Specifications
Heat Kit Electrical Data — 7½ Tons
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended | ||
Heat Kit Usage | at 208 / 240V | at 208 / 240V | at 240V | Airflow Range | ||
|
|
|
|
| ||
CPH090***3B*** | 40 | 50 |
|
| ||
74 | / 85 | 80 | / 90 | 15 | ||
113 | / 130 | 120 | / 150 | 30 | ||
147 | / 169 | 150 | / 175 | 43 | ||
|
|
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended |
Heat Kit Usage | at 208 / 240V | at 208 / 240V | at 240V | Airflow Range |
|
|
|
|
|
CPH090***4B*** | 19 | 25 |
|
|
42 | 45 | 15 | ||
64 | 70 | 30 | ||
84 | 90 | 43 | ||
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended |
Heat Kit Usage | at 208 / 240V | at 208 / 240V | at 240V | Airflow Range |
|
|
|
|
|
CPH090***7B*** | 14 | 15 |
|
|
32 | 35 | 15 | ||
51 | 60 | 30 | ||
68 | 70 | 43 | ||
|
|
|
|
|
¹ Minimum Circuit Ampacity |
|
|
|
|
² Maximum Overcurrent Protection device
KW Correction Factors
kW Correction Factor for
Supply Voltage | 240 | 230 | 220 |
| 210 | 208 | |||
|
|
|
|
|
|
|
|
|
|
Correction Factor | 1 | 0.93 | 0.82 |
| 0.78 | 0.76 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
kW Correction Factor for 480V Units |
|
|
| ||||||
Supply Voltage | 460 |
| 440 |
| 430 |
|
|
| |
|
|
|
|
|
|
|
|
| |
Correction Factor | 0.92 |
| 0.84 |
| 0.8 |
|
|
| |
|
|
|
|
|
|
|
|
|
|
For other voltage, use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage | 560 | 550 | 540 |
|
|
|
|
Correction Factor | 0.95 | 0.91 | 0.88 |
Multiply rated kW by correction factor to get actual kW.
Minimum Airflow for Electric Heat
Heater Size (kW) | Minimum CFM |
|
|
15 | 3,000 |
|
|
30 | 3,000 |
|
|
43 | 3,000 |
|
|
20 | www.goodmanmfg.com |