| Product Specifications | |
Heat Kit Electrical Data — 8½ Tons |
|
|
|
| ||
|
|
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended |
| Recommended |
Airflow Range |
| Airflow Range | ||||
Heat Kit Usage | at 240V | at 240V | at 240V |
| ||
(Downshot) |
| (Horizontal) | ||||
|
|
|
|
| ||
|
|
|
|
|
|
|
CPH102***3B*** | 43 | 50 |
|
|
|
|
88 | 90 | 15 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
133 | 150 | 35 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
173 | 175 | 43 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended |
| Recommended |
Airflow Range |
| Airflow Range | ||||
Heat Kit Usage | at 480V | at 480V | at 480V |
| ||
(Downshot) |
| (Horizontal) | ||||
|
|
|
|
| ||
|
|
|
|
|
|
|
CPH102***4B*** | 20 | 25 |
|
|
|
|
42 | 45 | 15 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
65 | 70 | 30 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
84 | 90 | 43 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended |
| Recommended |
Airflow Range |
| Airflow Range | ||||
Heat Kit Usage | at 575V | at 575V | at 575V |
| ||
(Downshot) |
| (Horizontal) | ||||
|
|
|
|
| ||
|
|
|
|
|
|
|
CPH102***7B*** | 17 | 20 |
|
|
|
|
36 | 40 | 15 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
55 | 60 | 30 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
71 | 80 | 43 | 3400 - 3825 CFM |
| 3400 - 3825 CFM | |
|
|
|
|
|
|
|
¹ Minimum Circuit Ampacity |
|
|
|
|
|
|
² Maximum Overcurrent Protection device
^ - EHK Heater Kits above require a
kW Correction Factor
kW Correction Factor (for 1- &
Supply Voltage | 240 | 230 | 220 | 210 | 208 |
|
|
|
|
|
|
Correction Factor | 1 | 0.93 | 0.82 | 0.78 | 0.76 |
|
|
|
|
|
|
kW Correction Factor for 480V Units
Actual Voltage | 460 | 440 |
| 430 |
|
|
|
|
|
Correction Factor | 0.92 | 0.84 |
| 0.8 |
|
|
|
|
|
For other voltage use voltage² / 480² |
|
|
| |
|
| |||
kW Correction Factor for 575V Units |
| |||
|
|
|
|
|
Supply Voltage | 560 | 550 |
| 540 |
|
|
|
|
|
Correction Factor | 0.95 | 0.91 |
| 0.88 |
|
|
|
|
|
Multiply rated kW by correction factor to get actual kW
Minimum Airflow for Electric Heat
Heater Size (kW) | Min. CFM | Min. CFM | |
Horizontal | |||
| |||
|
|
| |
15 | 3,400 | 3,400 | |
|
|
| |
30 | 3,400 | 3,400 | |
|
|
| |
43 | 3,400 | 3,400 | |
|
|
|
www.goodmanmfg.com | 21 |