Heat Kit Electrical Data — 8½ Tons

 

 

 

 

 

Product Specifications

Heat Kit Electrical Data — 8½ Tons

 

 

 

 

 

 

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

 

Recommended

Airflow Range

 

Airflow Range

Heat Kit Usage

at 240V

at 240V

at 240V

 

(Downshot)

 

(Horizontal)

 

 

 

 

 

 

 

 

 

 

 

 

CPH102***3B***

43

50

 

 

 

 

EHK3-16

88

90

15

3400 - 3825 CFM

 

3400 - 3825 CFM

EHK3-30

133

150

35

3400 - 3825 CFM

 

3400 - 3825 CFM

EHK3-45

173

175

43

3400 - 3825 CFM

 

3400 - 3825 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

 

Recommended

Airflow Range

 

Airflow Range

Heat Kit Usage

at 480V

at 480V

at 480V

 

(Downshot)

 

(Horizontal)

 

 

 

 

 

 

 

 

 

 

 

 

CPH102***4B***

20

25

 

 

 

 

EHK4-16

42

45

15

3400 - 3825 CFM

 

3400 - 3825 CFM

EHK4-30

65

70

30

3400 - 3825 CFM

 

3400 - 3825 CFM

EHK4-45

84

90

43

3400 - 3825 CFM

 

3400 - 3825 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

 

Recommended

Airflow Range

 

Airflow Range

Heat Kit Usage

at 575V

at 575V

at 575V

 

(Downshot)

 

(Horizontal)

 

 

 

 

 

 

 

 

 

 

 

 

CPH102***7B***

17

20

 

 

 

 

EHK7-16

36

40

15

3400 - 3825 CFM

 

3400 - 3825 CFM

EHK7-30

55

60

30

3400 - 3825 CFM

 

3400 - 3825 CFM

EHK7-45

71

80

43

3400 - 3825 CFM

 

3400 - 3825 CFM

 

 

 

 

 

 

 

¹ Minimum Circuit Ampacity

 

 

 

 

 

 

² Maximum Overcurrent Protection device

^ - EHK Heater Kits above require a three-phase power supply

kW Correction Factor

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

220

210

208

 

 

 

 

 

 

Correction Factor

1

0.93

0.82

0.78

0.76

 

 

 

 

 

 

kW Correction Factor for 480V Units

Actual Voltage

460

440

 

430

 

 

 

 

 

Correction Factor

0.92

0.84

 

0.8

 

 

 

 

 

For other voltage use voltage² / 480²

 

 

 

 

 

kW Correction Factor for 575V Units

 

 

 

 

 

 

Supply Voltage

560

550

 

540

 

 

 

 

 

Correction Factor

0.95

0.91

 

0.88

 

 

 

 

 

Multiply rated kW by correction factor to get actual kW

Minimum Airflow for Electric Heat

Heater Size (kW)

Min. CFM

Min. CFM

Down-shot

Horizontal

 

 

 

 

15

3,400

3,400

 

 

 

30

3,400

3,400

 

 

 

43

3,400

3,400

 

 

 

SS-CPH90-150

www.goodmanmfg.com

21

Page 21
Image 21
Goodman Mfg SS-CPH90-150 Heat Kit Electrical Data - 8½ Tons, kW Correction Factor, Minimum Airflow for Electric Heat

FAQ

What are the recommended airflow ranges for the EHK3-16 heat kit?

The recommended airflow range for the EHK3-16 heat kit at 240V is 3400-3825 CFM.

What is the minimum circuit ampacity for the CPH102***3B*** model?

The minimum circuit ampacity for the CPH102***3B*** model is 43.

Where can I find more information about the SS-CPH90-150 model?

You can find more information about the SS-CPH90-150 model on the Goodman Mfg official website.