Product Specifications
Product Specifications — 8½ Tons
| CPH102 | CPH102 | CPH102 |
| ***3B*** | ***4B*** | ***7B*** |
|
|
|
|
Cooling Capacity |
|
|
|
Total, BTU/h | 102,000 | 102,000 | 102,000 |
Sensible BTU/h | 73,440 | 73,440 | 73,440 |
EER / IEER | 11.1 / 11.2 | 11.1 / 11.2 | 11.1 / 11.2 |
Decibels | 83 | 83 | 83 |
ARI Reference #s | 3620224 | 3620224 | 3620224 |
Heating Capacity |
|
|
|
BTU/h (47°F) | 102,000 | 102,000 | 102,000 |
COP (47°F) | 3.4 | 3.4 | 3.4 |
BTU/h (17°F) | 55,500 | 55,500 | 55,500 |
COP (17°F) | 2.25 | 2.25 | 2.25 |
Evapoartor Motor / Coil |
|
|
|
Motor Type | Belt Drive | Belt Drive | Belt Drive |
Indoor Nominal CFM | 3,400 | 3,400 | 3,400 |
Indoor Motor FLA (Cooling) | 7.8 | 3.9 | 2.3 |
Horsepower - RPM | 1725 | 1725 | 1725 |
Piston Size (Cooling) | 0.08 | 0.08 | 0.08 |
Filter Size (Qty) | (4) 16” x 24” x 2” | (4) 16” x 24” x 2” | (4) 16” x 24” x 2” |
Drain Size (NPT) | 3/4” | 3/4” | 3/4” |
205 / 205 | 205 / 205 | 205 / 205 | |
Evaporator Coil Face Area (ft²) | 10.2 | 10.2 | 10.2 |
Rows Deep / Fins per Inch | 4 / 14 | 4 / 14 | 4 / 14 |
Belt Drive Evap Fan Data |
|
|
|
# of Wheels (D x W) | 1 (15” x 12”) | 1 (15” x 12”) | 1 (15” x 12”) |
Motor Sheave / Blower Sheave | VL40 / AK74 | VL40 / AK74 | VL40 / AK74 |
Belt | AX51 | AX51 | AX51 |
Condenser Fan / Coil |
|
|
|
Quantity of Condenser Fan Motors | 2 | 2 | 2 |
Horsepower - RPM | 1/4” - 1,090 | 1/4” - 890 | 1/4” - 1,075 |
Fan Diameter / # Fan Blades | 22 / 4 | 22 / 4 | 22 / 4 |
Outdoor Nominal CFM | 7,600 | 7,600 | 7,600 |
Face Area (ft²) | 16.19 | 16.19 | 16.19 |
Rows Deep / Fins per Inch | 2 / 22 | 2 / 22 | 2 / 22 |
Piston Size (Heating) | 0.059 | 0.059 | 0.059 |
Compressor |
|
|
|
Quantity / Type | 2 / Scroll | 2 / Scroll | 2 / Scroll |
Stage | 1 | 1 | 1 |
Compressor RLA / LRA ea. | 14.5 / 98 | 6.3 / 55 | 6.0 / 41 |
Electrical Data / Static |
|
|
|
Voltage / Phase / Frequency | 230 / 3 / 60 | 460 / 3 / 60 | 575 / 3 / 60 |
Standard Max Static | 1” | 1 | 1 |
Outdoor Fan FLA ea. | 1.4 | 0.8 | 0.6 |
Total Unit Amps | 39.6 | 18.1 | 15.5 |
Min. Circuit Ampacity¹ | 43.2 | 19.7 | 17 |
Max. Overcurrent Protection (amps)² | 50 | 25 | 20 |
Entrance Power Supply & Control Voltage | Locating Dimple | Locating Dimple | Locating Dimple |
Operating Weight (lbs) | 1285 | 1285 | 1285 |
Ship Weight (lbs) | 1310 | 1310 | 1310 |
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.
4 | www.goodmanmfg.com |