Goodman Mfg SS-CPH90-150 dimensions Heat Kit Electrical Data - 10 Tons, Product Specifications

Models: SS-CPH90-150

1 36
Download 36 pages 26.92 Kb
Page 22
Image 22
Heat Kit Electrical Data — 10 Tons

Product Specifications

Heat Kit Electrical Data — 10 Tons

Model and

MCA¹ at

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

208 / 240V

at 208 / 240V

at 240V

Airflow Range

 

 

 

 

 

CPH120***3B***

49

60

 

 

EHK3-16

81

/ 94

90 / 100

15

3500 - 4500 CFM

EHK3-30

122

/ 139

125 / 150

35

3500 - 4500 CFM

EHK3-45

154

/ 178

175 / 200

43

4000 - 4500 CFM

 

 

 

 

 

Model and

MCA¹ at

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

208 / 240V

at 208 / 240V

at 240V

Airflow Range

 

 

 

 

 

CPH120***3H***

50

60

 

 

EHK3-16

82

/ 95

90 / 100

15

---

EHK3-30

122

/ 140

125 / 150

35

---

EHK3-45

155

/ 179

175 / 200

43

---

 

 

 

 

 

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 480V

at 480V

at 480V

Airflow Range

 

 

 

 

 

CPH120***4B***

24

30

 

 

EHK4-16

46

50

15

3500 - 4500 CFM

EHK4-30

69

70

30

3500 - 4500 CFM

EHK4-45

89

90

43

4000 - 4500 CFM

 

 

 

 

 

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 575V

at 575V

at 575V

Airflow Range

 

 

 

 

 

CPH0120***7B***

17

20

 

 

EHK7-16

36

40

15

3500 - 4500 CFM

EHK7-30

55

60

30

3500 - 4500 CFM

EHK7-45

71

80

43

4000 - 4500 CFM

 

 

 

 

 

 

¹ Minimum Circuit Ampacity

 

 

 

 

 

² Maximum Overcurrent Protection device

kW Correction Factor

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

220

210

208

 

 

 

 

 

 

Correction Factor

1

0.93

0.82

0.78

0.76

 

 

 

 

 

 

kW Correction Factor for 480V Units

Actual Voltage

460

440

 

430

 

 

 

 

 

Correction Factor

0.92

0.84

 

0.8

 

 

 

 

 

For other voltage use voltage² / 480²

 

 

 

 

 

kW Correction Factor for 575V Units

 

 

 

 

 

 

Supply Voltage

560

550

 

540

 

 

 

 

 

Correction Factor

0.95

0.91

 

0.88

 

 

 

 

 

Multiply rated kW by correction factor to get actual kW

Minimum Airflow for Electric Heat

Heater Size (kW)

Min. CFM

Min. CFM

Down-shot

Horizontal

 

 

 

 

15

4,000

4,000

 

 

 

30

4,000

4,000

 

 

 

43

4,000

4,000

 

 

 

22

www.goodmanmfg.com

SS-CPH90-150

Page 22
Image 22
Goodman Mfg SS-CPH90-150 dimensions Heat Kit Electrical Data - 10 Tons, Product Specifications, kW Correction Factor

FAQ

What is the MOP amps for EHK3-16 heat kit at 240V?

The MOP amps for EHK3-16 heat kit at 240V is 15.

What is the correction factor for 575V supply voltage?

The correction factor for 575V supply voltage is 0.95.

How to determine the minimum airflow for electric heat for a 30 kW heater?

The minimum airflow for electric heat for a 30 kW heater is 4,000 CFM in both down-shot and horizontal configurations.