Goodman Mfg SS-CPH90-150 dimensions Product Specifications - 7½ Tons

Models: SS-CPH90-150

1 36
Download 36 pages 26.92 Kb
Page 3
Image 3
Product Specifications — 7½ Tons

 

 

 

 

Product Specifications

Product Specifications — 7½ Tons

 

 

 

 

 

 

 

 

 

 

 

 

CPH090

CPH090

CPH090

 

 

 

***3B***

***4B***

***7B***

 

 

 

 

 

 

 

Cooling Capacity

 

 

 

 

Total BTU/h

 

90,000

90,000

90,000

 

Sensible BTU/h

 

65,700

65,700

65,700

 

EER / IEER

 

11.5 / 11.2

11.5 / 11.2

11.5 / 11.2

 

IPLV

 

12.30

12.30

12.30

 

Decibels

 

83

83

83

 

AHRI Reference #s

 

3000984

3000984

3000984

 

Heating Capacity

 

 

 

 

 

BTU/h / COP (47° F)

 

90,000 / 3.5

90,000 / 3.5

90,000 / 3.5

 

BTU/h / COP (17° F)

 

55,500 / 2.4

55,500 / 2.4

56,500 / 2.4

 

Evaporator Motor / Coil

 

 

 

 

Motor Type

 

Belt Drive

Belt Drive

Belt Drive

 

Indoor Nominal CFM

 

3,000

3,000

3,000

 

Indoor Motor FLA (Cooling)

 

7.8

3.9

2.5

 

Horsepower - RPM

 

2.0 - 1725

2.0 - 1725

2.0 - 1725

 

Piston Size (Cooling)

 

0.076

0.076

0.078

 

Filter Size

 

16" x 24" x 2"

16" x 24" x 2"

16" x 24" x 2"

 

Drain Size (NPT)

 

¾"

¾"

¾"

 

R-410A Refrigerant Charge: Cir #1 / #2 (oz.)

 

215 / 215

215 / 215

200 / 200

 

Evaporator Coil Face Area (ft²)

 

10.2

10.2

10.2

 

Rows Deep / Fins per Inch

 

4 / 16

4 / 16

4 / 16

 

Belt Drive Evap Fan Data

 

 

 

 

# of Wheels (D x W)

 

1 (15" x 12")

1 (15" x 12")

1 (15" x 12")

 

Motor Sheave / Blower Sheave

 

VL40 / AK74

VL40 / AK74

VL40 / AK74

 

Belt

 

AX51

AX51

AX51

 

Condenser Fan / Coil

 

 

 

 

Quantity of Condenser Fan Motors

 

2

2

2

 

Horsepower - RPM

 

¼ - 1090

¼ - 890

¼ - 1075

 

Fan Diameter / # Fan Blades

 

22 / 4

22 / 4

22 / 4

 

Outdoor Expansion Device

 

0.052

0.052

0.055

 

Outdoor Nominal CFM

 

7,600

7,600

7,600

 

Face Area (ft²)

 

32.4

32.4

32.4

 

# Coils / Rows Deep - Fins per Inch

 

2 / 2 - 20

2 / 2 - 20

2 / 2 - 20

 

Piston Size (Heating)

 

0.052

0.052

0.055

 

Compressor

 

 

 

 

Quantity / Type / Stage

 

2 / Scroll / 1

2 / Scroll / 1

2 / Scroll / 1

 

Compressor RLA / LRA

 

13.1 / 83.1

6.1 / 41.0

4.4 / 33.0

 

Electrical Data

 

 

 

 

Voltage / Phase / Frequency

 

208-230 / 3 / 60

460 / 3 / 60

575 / 3 / 60

 

Indoor Blower HP / FLA

 

1.5 / 5.0

1.5 / 2.5

2 / 2.5

 

Outdoor Fan HP / FLA

 

¼ / 1.4

¼ / 0.8

¼ / 0.6

 

Total Unit Amps

 

36.9

17.7

12.5

 

Min. Circuit Ampacity¹

 

40

19

13.6

 

Max. Overcurrent Protection (amps)²

 

50

25

15

 

Entrance Power Supply & Control Voltage

 

 

Locating Dimple

 

 

Operating Weight (lbs)

 

1135

1135

1135

 

Ship Weight (lbs)

 

1175

1175

1175

 

¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted.

Note: Always check the S&R plate for electrical data on the unit being installed.

SS-CPH90-150

www.goodmanmfg.com

3

Page 3
Image 3
Goodman Mfg SS-CPH90-150 dimensions Product Specifications - 7½ Tons

FAQ

What are the cooling and heating capacities of the Goodman Mfg SS-CPH90-150 Air Conditioner?

The cooling capacity is 90,000 BTU/h with EER/IEER of 11.5/11.2. The heating capacity is 90,000 BTU/h/COP 47 F and 55,500 BTU/h/COP 17 F.

What type of motor does the evaporator fan of the Goodman Mfg SS-CPH90-150 Air Conditioner have?

The evaporator fan of the Goodman Mfg SS-CPH90-150 Air Conditioner has a belt drive motor.

What are the electrical specifications for the Goodman Mfg SS-CPH90-150 Air Conditioner?

The unit operates on 208-230V/3/60Hz and has a total unit amp of 36.9. Minimum circuit ampacity is 40 and max overcurrent protection amps is 50.