Product Specifications
Heat Kit Electrical Data — 12½ Tons
Model and | MCA¹ at | MOP² (amps) | Actual kW | Recommended |
Heat Kit Usage | 208 / 240V | at 208 / 240V | at 240V | Airflow Range |
|
|
|
|
|
CPH150***3B*** | 65 | 80 |
|
|
110 | 110 | 15 | 4000 - 5600 | |
155 | 175 | 30 | 4300 - 5600 | |
194 | 200 | 43 | 4500 - 5600 | |
|
|
|
|
|
|
|
|
|
|
Model and | MCA¹ at | MOP² (amps) | Actual kW | Recommended |
Heat Kit Usage | 208 / 240V | at 208 / 240V | at 240V | Airflow Range |
|
|
|
|
|
CPH150***4B*** | 31 | 40 |
|
|
54 | 60 | 15 | 4000 - 5600 | |
76 | 80 | 30 | 4300 - 5600 | |
96 | 100 | 43 | 4500 - 5600 | |
|
|
|
|
|
|
|
|
|
|
Model and | MCA¹ at | MOP² (amps) | Actual kW | Recommended |
Heat Kit Usage | 208 / 240V | at 208 / 240V | at 240V | Airflow Range |
|
|
|
|
|
CPH150***7B*** | 23 | 30 |
|
|
42 | 45 | 15 | 4000 - 5600 | |
61 | 70 | 30 | 4300 - 5600 | |
77 | 80 | 43 | 4500 - 5600 | |
|
|
|
|
|
¹ Minimum Circuit Ampacity (standard drive)
² Maximum Overcurrent Protection device (standard drive)
KW Correction Factors
kW Correction Factor for 1- &
Supply Voltage | 240 | 230 |
| 220 | 210 | 208 |
Correction Factor | 1 | 0.93 |
| 0.82 | 0.78 | 0.76 |
|
|
|
| |||
kW Correction Factor for 480V Units |
|
|
| |||
|
|
|
|
|
|
|
Supply Voltage | 460 | 440 |
| 430 |
|
|
|
|
|
|
|
|
|
Correction Factor | 0.92 | 0.84 |
| 0.8 |
|
|
|
|
|
|
|
|
|
For other voltage, use voltage² / 480² |
|
|
|
|
| |
|
|
|
| |||
kW Correction Factor for 575V Units |
|
|
| |||
|
|
|
|
|
|
|
Supply Voltage | 560 | 550 |
| 540 |
|
|
|
|
|
|
|
|
|
Correction Factor | 0.95 | 0.91 |
| 0.88 |
|
|
|
|
|
|
|
|
|
Multiply rated kW by correction factor to get actual kW.
www.goodmanmfg.com | 23 |