Honeywell Model VR9205 Connected to Manometer
1.Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.
2.Connect a calibrated water manometer (or appropriate gas pressure gauge) at either the gas valve inlet pressure boss or the gas piping drip leg. See Honeywell VR9205 gas valve figure or
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| High Fire |
Regulator |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Regulator | ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Adjust | |||||||||||||||||
Vent |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Gas Valve On/Off
Selector SwitchLow Fire
Regulator
Adjust
Honeywell Model VR9205
NOTE: If measuring gas pressure at the drip leg or Honeywell VR9205 gas valve, a
3.Turn ON the gas supply and operate the furnace and all other gas consuming appliances on the same gas supply line.
4.Measure furnace gas supply pressure with burners firing. Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table.
Inlet Gas Supply Pressure
Natural Gas | Minimum: 5.0" w.c. | Maximum:10.0" w.c. |
Propane Gas | Minimum: 11.0" w.c. | Maximum:13.0" w.c. |
If supply pressure differs from table, make the necessary ad- justments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.
5.Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer. Reinstall plug before turning on gas to furnace.
6.Turn OFF any unnecessary gas appliances stated in step 3.