Goodman Mfg VC8 Start-Up Procedure And Adjustment, Gas Valve On/Off Selector Switch

Models: VC8

1 48
Download 48 pages 50.02 Kb
Page 24
Image 24
Gas Valve On/Off

START-UP PROCEDURE AND ADJUSTMENT

INLET

OUTLET

Gas Valve On/Off

Selector Switch

White-Rodgers Model 36G54 (Two-Stage)

Open to

Manometer

 

 

 

Atmosphere

Hose

 

 

 

 

 

 

 

 

 

 

Outlet

High Fire Regulator

 

 

 

Adjust

 

 

 

Pressure Boss

 

 

Regulator

 

 

 

 

 

 

Vent

 

 

 

 

Open to

Manometer

Atmosphere

Hose

i

Manometer

Common

Terminal(C)

High Fire Coil

Terminal (HI)

Low Fire Coil

Terminal (LO)

Inlet Pressure Tap 1/8 NPT

Outlet Pressure Tap 1/8 NPT

Inlet

 

Pressure

Boss

High Fire Coil

Manometer

Terminal (HI)

 

 

On/Off Switch

Low Fire

Regulator

Adjust

Coaxial Coil

Terminal (M)

Common

Terminal(C)

Honeywell Model VR9205 Connected to Manometer

1.Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace.

2.Connect a calibrated water manometer (or appropriate gas pressure gauge) at either the gas valve inlet pressure boss or the gas piping drip leg. See Honeywell VR9205 gas valve figure or White-Rodgers 36G54 gas valve figure for location of inlet pressure boss.

White-Rodgers Model 36G54 Connected to Manometer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Fire

Regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjust

Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Valve On/Off

Selector SwitchLow Fire

Regulator

Adjust

Honeywell Model VR9205 (Two-Stage)

NOTE: If measuring gas pressure at the drip leg or Honeywell VR9205 gas valve, a field-supplied hose barb fitting must be installed prior to making the hose connection. If using the inlet pressure boss on the White-Rodgers 36G54 gas valve, then use the 36G Valve Pressure Check Kit, Goodman Part No. 0151K00000S.

3.Turn ON the gas supply and operate the furnace and all other gas consuming appliances on the same gas supply line.

4.Measure furnace gas supply pressure with burners firing. Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table.

Inlet Gas Supply Pressure

Natural Gas

Minimum: 5.0" w.c.

Maximum:10.0" w.c.

Propane Gas

Minimum: 11.0" w.c.

Maximum:13.0" w.c.

If supply pressure differs from table, make the necessary ad- justments to pressure regulator, gas piping size, etc., and/or consult with local gas utility.

5.Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer. Reinstall plug before turning on gas to furnace.

6.Turn OFF any unnecessary gas appliances stated in step 3.

24

Page 24
Image 24
Goodman Mfg VC8 instruction manual Start-Up Procedure And Adjustment, Gas Valve On/Off Selector Switch